1.7 RTCC (Real Time Clock Calendar)
The device has a real time clock calendar. The time is synchronized continuously when connected to the server.
1.8 Data Logging and Measurement Interval
The values of every measurement are saved in the memory with the time stamp. At a measurement interval of
one minute, it is possible to save data of one month, which corresponds to 44,000 pairs of measured values.
When the ring memory is full, the oldest values are overwritten.
1.9 Indicator and Button
The device has a button and multicolour LED for use and indication of the operating state. The button is used
to start the device or switch it off in battery mode. The LED indicates the device status and whether it was
possible in the current measurement interval to carry out a valid measurement and send the data to the
monitoring system.
LED Status Indicator for LAN Devices
Pairing
Trigger
Action
LED
1s press
Confirms pairing
n x orange, the LED flashes
orange
when
the
pairing
demand is open
Remove pairing
Trigger
Action
LED
8s press
Removes pairing, stops logging
and turns off device
3 x red, the pairing information
stored in the logger is deleted
Device status update
Trigger
Action
LED
1s press
Shows the current status
1 x green, the connection to the
server is good
1 x red, battery low
2 x red, there is no connection
to the server
Automatic (every 5 seconds)
Shows the current status
1 x green, the connection to the
server is good
2 x red, there is no connection
to the server
LED Status Indicator for Wireless Devices