13

INSTRUCTIONS FOR THE REPLACEMENT OF PREVIOUS DRIVES WITH ACTUAL TYPE CODE 119/92

Drive code 119/92 replaces previous drives for the Rowan single phase motors type code 119 and code 120/121.
Remember that in any case code 119/92-2HP board is necessary for the single phase motor 2HP Mec 100.

Replacing drive 119 with drive 119/92:

With regard to power connections:
the wires previously connected to terminals 7 and 8 are to be shifted to terminals 11 and 12 of the code 119/92,
whereas the wires connected to terminals 5 and 6 are to be shifted to terminals 9 and 10.
With regard to control connections:
the tachometer  wires that were previously connected to terminals 3 and 4 are to be connected to terminals 7 and
8 of the code 119/92, whereas potentiometer wires as follows: P- (OV) connected to terminal 2 is to be shifted to
terminal 6, and P+ connected to terminal 1 is to be shifted to terminal 5 of the code 119/92. For functioning as old
card cod. 119, microswitch S3 must be closed.
With new drive C119/92, speed regulation with 2 wire potentiometer is not linear but according to an exponential
curve which presents strong variations at slow speed and small variations at high speed. If one wishes to avoid this
behaviour and obtain a variation directly proportional to potentiometer variation, it is necessary to connect speed
potentiometer with 3 wires as  indicated in connection diagram of code 119/92 and open microswitch S3.
With regard to control wires connected to the lateral terminal strip of code 119:
- the wire connected to terminal NEG is to be shifted to terminal 1 of the code 119/92
- the wire connected to terminal AR is to be shifted to terminal 2 of the code 119/92
- the wire connected to terminal INV.TACH. is to be omitted (not necessary for the C119/92)
- the resistor connected to terminal REG. COPPIA must be eliminated.
Close microswitch S1 (for the other microswitches refer to the section containing the description of the
microswitches).
If a potentiometer is connected to torque regulation terminals, reconnect it to code C119/92 with 3 wires to terminals
1 3 4 as from electrical drawing; in this case microswitch S2 must be closed.
The circled numbers in the electrical drawing designate the terminals in the code C119/92.

Reg. Coppia = Torque Regulation

Reg. Giri =  Speed Regulation

Tachim.= Tachometer Generator

Linea = Mains Line

Negativo = Negative

Azz. Rampa = Ramp to zero setting

Inv. Tach. = Tachometer Inversion

Summary of Contents for 119/92

Page 1: ...NUAL CODE119 92 REV 7 Date 15 10 18 EMC CONFORMITY FORASYNCHRONOUS ROWAN SINGLE PHASE MOTORS with TACHOMETER Motori azionamenti accessorieserviziperl automazione Via Ugo foscolo 20 CALDOGNO VICENZA IT...

Page 2: ...any inaccuracies contained in this manual due to printing and or transcription errors ROWAN ELETTRONICA s r l reserves the right to make any variations that it considers necessary for better function...

Page 3: ...ally through potentiometer or 0 10Vdc signal Input for pure contact or NPN open collector transistor for static run stop command 12Vdc 2mA Internal regulations through trimmer for acceleration deceler...

Page 4: ...ed system extremely silent Absence of typical PWM whistle and uniform from zero to the maximum motor rounds The application of controlled diodes on the power part gives reliability against extravoltag...

Page 5: ...3kohm load regulation external potentiometers 1 5 speed regulation 0 10VDC signal input 0VDC zero turns 10VDC max speed 1 extreme 3 cursor torque limitation external potentiometer connection 4 extreme...

Page 6: ...terorfrom0 10VDCsignalconnectedtoterminal3 closed activates board internal torque limitation from trimmer P1 S2 open cuts out torque limitation closed activatestorquelimitation S3 open in case of 3 wi...

Page 7: ...l it can be used for analog revolution counters display counters or other servomechanisms provided the overall loading being not lower than 5Kohm maxtachometercurrent 5mA Itisalwaysnecessary toavoidin...

Page 8: ...te it means that tachometer dynamo voltage is not reaching terminals 7 and 8 when this happens check the connections again Check attainment of maximum speed and if necessary fine adjust the maximum va...

Page 9: ...oswitch S1 and limit torque by regulating trimmer P1 Speed torque control from analog signal 0 10VDC In code 119 92 speed and torque regulations in addition to the conventional manual potentiometer ca...

Page 10: ...sets the ramp and switches off RUN led L2 If motor run stop were necessary with acceleration and deceleration ramps without immediately removing voltage from the motor in its stopping phase perform th...

Page 11: ...ve the screws attaching the brake to the hub 4 disconnect the brake cable from the terminal block 5 slide the brake off the hub At this stage the calibration can be made by adjusting the 3 bolts until...

Page 12: ...of motor windings with relative terminal board covering 9 FEET for B3 or B3 B5 versions 10 THERMICSENSORINSIDEWINDINGS 11 COMPENSATORRING 12 REAR RING for rear bearing housing 13 SERVICE TERMINAL BOA...

Page 13: ...r but according to an exponential curvewhichpresentsstrongvariationsatslowspeedandsmallvariationsathighspeed Ifonewishestoavoidthis behaviour and obtain a variation directly proportional to potentiome...

Page 14: ...of board C120 121 proceed as follows shift the wire connected to terminal NEG to terminal 1 of C119 92 shift the wire connected to terminal AR to terminal 2 of C119 92 exclude the wire connected to t...

Page 15: ...ROWAN ELETTRONICA S R L Via Ugo Foscolo 20 36030 CALDOGNO VICENZA ITALY BLOCK DIAGRAM...

Page 16: ...Foscolo 20 36030 CALDOGNO VICENZA ITALY EMC CONFORMITY Motori azionamenti accessorieserviziperl automazione Via Ugo foscolo 20 CALDOGNO VICENZA ITALY Tel 0039 444 905566 Fax 0039 444 905593 E mail inf...

Reviews: