25
Insert the cables through the
frame.
31
Drop the stayplate on top of
the last module. Make sure the
combinations of modules equal
the 160 mm packing space.
30
Lift up the stayplate and insert
the last module underneath it.
29
Before inserting the final module,
insert a stayplate.
32
Use a Roxtec pre-compression
tool to make space for the
compression units if required.
Insert the compression units until
stop. Do not tighten the first
compression unit until the second
compression unit is inserted.
35
The compression units can be
placed with the screwhead facing
the inside (B) or the outside (A) of
the frame.
A
B
36
26
When placing cables in modules,
the cable armor shall be visible
outside the module at the
termination side.
27
Place cables, according to your
packing plan, in the module
halves. Place corresponding
module halves on top.
28
For pass-through cables, cable
armor shall be visible on the
termination side.
Lubricate the sealing surfaces of
the compression units.
34
Turn the screw of the compression
units counter-clockwise to full stop.
33