38
Visible excess lubricant is a sign
of good compression. Make
sure that all modules are placed
correctly and fully inserted after
compression.
39
If applicable, check that the
protective bonding conductor is
correctly installed.
40
Verify earth continuity from each
cable armor to the earthing
terminal using a suitable
instrument.
37
Tighten the screws of the
compression units alternately
until full stop, approx. 20 Nm.