9. 

Trouble shooting 

 
 

Before requesting service, please check the following: 

 

If the appliance is not working at all please check whether: 
 

  The power supply is interrupted   .................................................. 

Self-checking

 

  A fuse has blown     ....................................................................... 

Self-checking

 

  The plug is firmly in the socket  ..................................................... 

Self-checking

 

  Power has been switched on    ..................................................... 

Self-checking

 

  The electronic has been properly set    ......................................... 

Self-checking

 

 
The refrigeration equipment is working, but incorrect: 
 

The products are too warm or too cold: 

  Is the condenser clean?   ............................................................... 

Self-checking

 

  Is the surrounding temperature too high?  ..................................... 

Self-checking

 

  Is there too much food or is it too warm?  ...................................... 

Self-checking

 

  Has the evaporator not been defrosted?  ...................................... 

Self-checking

 

  The refrigerated well is subject to strong draughts   ..................... 

Self-checking

 

  The cooling unit is malfunctioning   ................................................ 

Customer service

 

  The cooling regulator is set wrong   ............................................... 

Customer service

 

 

The evaporators are constantly iced up: 

  Defrosting does not begin    ........................................................... 

Customer service

 

  The ventilators are not running   .................................................... 

Customer service

 

  The air circulation in the well is blocked   .......................................  C

lear the ventilation openings

 

 

 

 

Status display and error notification 
 

Message 

Cause 

Error elimination  

Temperature 
indication flashes

 

Refrigerating chamber temperature 
beyond alarm limits (parameter A1 
A2) 

 

E0 

flashes 

Refrigerating chamber sensor F1 
error, break or short-circuit 

Control sensor. Controller operates 
according to with parameter c3. 

E1 

flashes 

Sensor F2 error, 
break or short-circuit 

Control sensor. At setting [c3=1] the 
controller operates in timed defrosting 
modus (defrosting time as set in d3). 

EP 

flashes 

Data loss at parameter memory 
 

Unplug the appliance. Press and hold 
down buttons (4) SET and (1) UP and plug 
the power plug back into the socket.  By 
doing so the electronic will re-program 
itself. 

If Error occurs again please contact 
customer service. 

 
Should the options listed not be the cause of the error, please contact customer service. 
 

IMPORTANT:

 

 

 

THE MANUFACTURER IS NOT LIABLE FOR LOSS OF GOODS, EVEN IF 

THE APPLIANCE IS STILL COVERED BY WARRANTY.   

IT IS THEREFORE RECOMMENDED THAT THE TEMPERATURE OF THE 

APPLIANCE BE CHECKED PERIODICALLY.   

Summary of Contents for VIENNA Air Screen

Page 1: ...Operating and Maintenance instructions Please read this manual carefully before you start to operate your cooling equipment Following the instructions helps to ensure the unit is fully functional at a...

Page 2: ...of the unit 4 5 Safety notes 4 6 Fundamental operating notes 5 6 1 Switching on the appliance 5 6 2 Setting the temperature 5 6 3 Manual defrosting 5 6 4 Lighting 5 7 Operating description 6 7 1 Load...

Page 3: ...a qualified refrigeration technician Air currents near the refrigerating unit resulting from improperly installed ventilation or draughts are to be avoided in order to ensure the efficient functioning...

Page 4: ...can lead to property damages This symbol points to operation tips and especially useful information of optimal use 1 5 Validity These operating instructions are valid for the models VIENNA Closed Disp...

Page 5: ...those intended are to be considered as not being in compliance with the regulations The manufacturer supplier is not liable for any damages resulting from such actions The user bears the entire risk U...

Page 6: ...refrigerated display case is set at a temperature of 39 F Your desired temperature can be set by holding down the SET button 4 and simultaneously pressing UP button 1 for higher temperatures or DOWN b...

Page 7: ...portant to leave adequate free space for the refrigerated air to circulate within the display case Products should be kept clear of the shaded areas shown in the picture A minimum clearance of 1 shoul...

Page 8: ...the bracket in the new position 4 Choose level slant position Display cases with drawer element Models Gastro L and Gastro SL and series Green L and Green SL are equipped with a drawer which offers ea...

Page 9: ...these parts It is absolutely necessary to bear some fundamental things in mind to keep this stainless steel unit working and to maintain its long life always keep the stainless steel surface clean ma...

Page 10: ...rior have to be cleaned with lukewarm soap water Always dry the interior after cleaning After cleaning lift the evaporator remove the lock and drop the evaporator back in its original position Insert...

Page 11: ...2 in and outside ATTENTION Hold glass during opening and cleaning Don t let the glass top fall down Hold the glass and bring it back in end position Front glasses made of insulated double glass Pictur...

Page 12: ...stomer service The ventilators are not running Customer service The air circulation in the well is blocked Clear the ventilation openings Status display and error notification Message Cause Error elim...

Page 13: ...ediately by a specialized service representative 11 Maintenance In order to guarantee efficient operation of the refrigerated well along with optimum presentation of the goods the entire technological...

Page 14: ...11 2011 Technical changes reserved Page 13 Doc OM_VIAS VICD 10D 12 Wiring diagram Wiring diagram VICD and VIAS self contained 115 V 1 PH 60 Hz Wiring diagram VICD and VIAS remote refrigerated 115 V 1...

Page 15: ...Valid from 11 2011 Technical changes reserved Page 14 Doc OM_VIAS VICD 10D Wiring diagram VICD and VIAS self contained 115 208 230 V 1 PH 60 Hz...

Page 16: ...ng diagram VICD and VIAS self contained 115 V 1 PH 60 Hz With rear ventilation Kit including time relay for longer runtime of the fan Wiring diagram VICD and VIAS self contained 115 208 230 V 1 PH 60...

Page 17: ...P a r t s S e r v i c ed i r e c t 1 8 6 6 7 2 7 0 7 2 1 S e r v i c eE ma i l s e r v i c e r p i i n d u s t r i e s c o m P a r t s E ma i l p a r t s r p i i n d u s t r i e s c o m...

Reviews: