Valid from: 11/2011
Technical changes reserved
Page 11
Doc.: OM_VIAS & VICD (10D)
9.
Trouble shooting
Before requesting service, please check the following:
If the appliance is not working at all please check whether:
The power supply is interrupted ..................................................
Self-checking
A fuse has blown .......................................................................
Self-checking
The plug is firmly in the socket .....................................................
Self-checking
Power has been switched on .....................................................
Self-checking
The electronic has been properly set .........................................
Self-checking
The refrigeration equipment is working, but incorrect:
The products are too warm or too cold:
Is the condenser clean? ...............................................................
Self-checking
Is the surrounding temperature too high? .....................................
Self-checking
Is there too much food or is it too warm? ......................................
Self-checking
Has the evaporator not been defrosted? ......................................
Self-checking
The refrigerated well is subject to strong draughts .....................
Self-checking
The cooling unit is malfunctioning ................................................
Customer service
The cooling regulator is set wrong ...............................................
Customer service
The evaporators are constantly iced up:
Defrosting does not begin ...........................................................
Customer service
The ventilators are not running ....................................................
Customer service
The air circulation in the well is blocked ....................................... C
lear the ventilation openings
Status display and error notification
Message
Cause
Error elimination
Temperature
indication flashes
Refrigerating chamber temperature
beyond alarm limits (parameter A1
A2)
E0
flashes
Refrigerating chamber sensor F1
error, break or short-circuit
Control sensor. Controller operates
according to with parameter c3.
E1
flashes
Sensor F2 error,
break or short-circuit
Control sensor. At setting [c3=1] the
controller operates in timed defrosting
modus (defrosting time as set in d3).
EP
flashes
Data loss at parameter memory
Unplug the appliance. Press and hold
down buttons (4) SET and (1) UP and plug
the power plug back into the socket. By
doing so the electronic will re-program
itself.
If Error occurs again please contact
customer service.
Should the options listed not be the cause of the error, please contact customer service.
IMPORTANT:
THE MANUFACTURER IS NOT LIABLE FOR LOSS OF GOODS, EVEN IF
THE APPLIANCE IS STILL COVERED BY WARRANTY.
IT IS THEREFORE RECOMMENDED THAT THE TEMPERATURE OF THE
APPLIANCE BE CHECKED PERIODICALLY.