IDM 98IV
&
99IV / EN
17
Weight :
460g (including battery)
Dimensions (W x H x D) :
94mm x190mm x 48mm with holster.
Accessories :
Battery (installed), Test leads and user manual.
(The probe assembly provided with the product are for use with
this product)
Pollution degree :
2
EMC :
EN 61326-1
Shock vibration :
Sinusoidal vibration per MIL-PRF- 28800F
(5 ~ 55 Hz, 3g max.)
Drop Protection :
4 feet drop to hardwood on concrete floor.
Indoor use only.
Electrical Specifications
Accuracy is ±(% r number of digits) at 23°C ± 5°C
< 80%RH.
AC Function
ACV and ACA specifications are ac coupled, true R.M.S.
The crest factor may be up to 3.0 at 4000 counts.
For non-sinusoidal waveforms, Additional Accuracy by
Crest Factor (C.F.) :
Add 3.0% for C.F. 1.0 ~ 2.0.
Add 5.0% for C.F. 2.0 ~ 2.5.
Add 7.0% for C.F. 2.5 ~ 3.0.
(1) DC mV Voltage
Range
Resolution
For 98IV
Accuracy
For 99IV
Accuracy
60.00mV
DC
0.01mV
± (
0.1% + 5d)
± (
0.08% + 5d)
600.0mV
DC
0.1mV
± (
0.1% + 2d)
± (
0.08% + 2d)
Input Impedance :
10MΩ
Overload Protection :
AC/DC1000V
(2) AC Voltage
Range Resolution
For 98IV
Accuracy
For 99IV
Accuracy
Frequency
Response
600.0mV
AC
0.1mV
± (
1.5% + 10d)
± (
1.2% + 10d)
45 ~ 500Hz
6.000V
AC
0.001V
± (
1.0% + 5d)
± (
0.8% + 5d)
60.00V
AC
0.01V
± (
1.0% + 5d)
± (
0.8% + 5d)
45 ~ 1KHz
600.0V
AC
0.1V
± (
1.0% + 5d)
± (
0.8% + 5d)
1000V
AC
1V
± (
1.0% + 5d)
± (
0.8% + 5d)