background image

SAFETY TERMS AND SYMBOLS

These terms may appear in this manual or on the product:

WARNING. Warning statements identify conditions or practices that

could result in injury or loss of life.

CAUTION. Caution statements identify conditions or practices that could

result in damage to this product or other property.

 
                     

The following symbols may appear in this manual or on the product:

  

     

   

DANGER
High Voltage

   DANGER
   Hot Surface

  ATTENTION
  refer to Manual

Protective
Conductor
Terminal

Equipotentiality

DC  POWER  SUPPLY

ALIMENTATION C.C

.

ISO-TECH

  IPS 303A

201-3424

ISO-TECH

  IPS 601A

201-3446

Summary of Contents for Iso-tech IPS 303A

Page 1: ...AUTION Caution statements identify conditions or practices that could result in damage to this product or other property The following symbols may appear in this manual or on the product DANGER High V...

Page 2: ...ent persons WARNING THIS APPLIANCE MUST BE EARTHED IMPORTANT The wires in this lead are coloured in accordance with the following code Green Yellow Earth Blue Neutral Brown Live Phase As the colours o...

Page 3: ...eter 3 2 5 Insulation 3 3 PANEL CONTROLS AND INDICATORS 4 3 1 Front Panel 4 3 2 Rear Panel 4 4 OPERATION INSTRUCTIONS 7 4 1 Precaution 7 4 2 Setting Current Limit 7 4 3 Constant Voltage Constant Curre...

Page 4: ...a coarse and fine potentiometer Both outputs can be accurately read on the voltmeter and ammeter Both stability and ripple are extremely good to meet the requirements of modern circuit design The unit...

Page 5: ...ature Humidity 10 C to 70 C 70 Maximum Altitude 2000m Installation Category II Pollution Degree 2 Product Designed for Indoor use only Accessories Fuse 1 Test lead GTL 105 current 4A 1 GTL 104 4A curr...

Page 6: ...Hz 1MHz rating current 3A Ripple Noise 1 0mVrms 5Hz 1MHz rating current 3A 5 Temperature coefficient 300ppm C 2 3 Constant Current Operation 1 Output current range 0 to rating current continuously adj...

Page 7: ...meter indicates the output current Analog type 12 A V selects switch selects whether he meter indicates the output voltage or current 13 Power control on off switch 14 Current HI LO control current in...

Page 8: ...E5 FIG 3 1 Front Panel...

Page 9: ...E6 FIG 3 2 Rear Panel...

Page 10: ...the current value on the Ammeter 5 The current limit overload protection has now been preset Do not change the CURRENT control setting after this step 6 Remove the short between the and terminals and...

Page 11: ...lt battery Initially the open circuit voltage of the power supply may be preset for 13 8 volts A low battery will place a heavy load on the supply and it will operate in the constant current mode whic...

Page 12: ...s when using identical models Two power supplies can be connected in series to provide a higher voltage and rating current output See Fig 4 2 for the connection scheme A Set power switch to OFF positi...

Page 13: ...E10 Fig 4 2 Connecting Two Power Supplies in Series...

Page 14: ...Set power switch to OFF position B Set the MASTER power supply INT SLAVE switch to INT position and set the SLAVE power supply INT SLAVE switch to PAR SLAVE position C Create a link from the MASTER p...

Page 15: ...E12 Fig 4 3 Connecting Two Power Supplies in Parallel...

Page 16: ...ltage source is connected to the SER input terminal and the line of control voltage source is connected to the power supply output terminal C The output voltage Eo is calculated as follows Eo Output v...

Page 17: ...The output current Io is calculated as follows Io Output current of the power supply Ir Rated current of the power supply Ec Remote control voltage 0 Ec approx 10V D For the remote control voltage sou...

Page 18: ...version The primary winding of the power transformer is tapped to permit operation from 100 120 220 or 230 VAC 50 60 Hz line voltage Conversion from one line voltage to another is done by changing AC...

Page 19: ...imeter to measure DC current at the output terminals of the power supply C Set the COARSE and FINE CURRENT controls to minimum fully counterclockwise D Adjust trimmer pot VR107 for a reading of 0 amps...

Page 20: ...E17 Fig 5 1 Adjustment Location...

Page 21: ...E18 Fig 5 2 Adjustment Location...