Input mode C

CP1, CP2 Quadrature inputs from shaft encoder or
similar. If CP1 leads CP2 then counter increments; if
CP2 leads CP1 then counter decrements.

Note:

Link TC should not be connected when in counter mode.

Timer

Operating mode N

The display shows the elapsed time until the set time is reached. At this
point the output is turned on the display is held. This continues until a
reset is applied.

Operating mode F

Operation is for mode N except that the display continues to show the
elapsed time when the set time is reached.

Operating mode C

The display shows the elapsed time until the set time is reached. At this
point the output is turned on for 0.5sec., the timer is reset, and timing
begins again immediately.

Note:

In this mode the unit should not be used in such a way that the set
time is reached during the timed output period.

Operating mode R

Operation is as for mode C except that the timer is held in reset until the
timed output has elapsed.

CP1

Initiates a timing sequence when the input is turned on. For single
operations only, a single pulse is required. In modes C and R a
continuous input will cause cyclic operation.

CP2

Gates the timing. When this input is on, the timing is suspended.

TC

This input controls the timing action during power supply failure. If
TC is on (connected to terminal 3) timing is suspended during
power failure; if TC is off, timing will continue regardless of the
power supply.

Setting up

1. Link terminal 1 to terminal 3
2. Use the 

key to stop through the modes i.e. counter or timer

functions; hours, min, sec, are timer functions

3. Press the 

key to store the displayed mode

4. Use the 

key to step through the input modes A, B, and C.

Note:

Where the timer was previously selected, the display will show ‘T’
and no other mode will be possible

5. Press the 

key to store the display mode

6. Use the 

key to step through the output modes N, F, C and R

7. Press the 

key to store the display mode

8. Disconnect terminal 1 from terminal 3

Set point

1. Ensure terminal 1 is disconnected from terminal 3
2. Press the 

key

3. Use the 

key to select the desired value for most

significant digit

4. Press the 

key

5. Repeat steps 3 and 4 for each digit

Application notes

1. The timer can be gated through CP2, with CP1 serving as a trigger

input, to perform a time integrating function.

2. This unit uses a transformerless power supply and inputs may

therefore be at high potential. Extreme personal care should be
exercised when connecting external components. Where possible an
isolating transformer or low voltage supply should be used when
connecting to low voltage switching devices or sensors. Ensure any
devices connected to these input terminals have an insulation
appropriate to the power supply voltage.

3. The internal circuit will be destroyed when either of the two mistakes

indicated on the right figure are made. An isolating transformer is
necessary, and the input should not be earthed.

4. Programming can take with power on or off. If you have the option we

suggest power off.

5. Shorting link between 3 & 4 with TIMER function will halt the “time

out”. Terminals 3 & 4 should be open for COUNTER function.

Technical specification

Count range: ____________________________0-999999 counts
Time ranges: ______________________________0.9999.99 secs

0-99999.9 mins

0-99999.9 hours

RS

stock no.

312-353

312-369

Supply voltages:

24-240V a.c.

12-120V d.c.

Supply voltage range:

90% to 110% of rated voltage

Power consumption:

1.3VA at 240V

1W at 120V

Inrush current (0.5ms)

3.7A

2.3A

Supply frequency range:

50/60Hz

-

Supply ripple factor:

-

20% max.

Count speed:

30Hz

1kHz

Pulse width, min:

16.7ms

0.5ms

Short circuit impedance:

10k

½

max. (inputs 5,6,7) s/c current: 1mA 

max.

Short circuit residual 
voltage:__________________________________0.5V max. (inputs 5,6,7)
Open circuit impedance: ______500k

½

min. (inputs 5,6,7) o/c voltage:

20V max.

Reset time: __________________________________________20ms min
Repeat accuracy: ___________________0.05% ± 0.005 secs.
Setting error: ______________________________± 0.1% ± 0.005 secs.
Service life

- mechanical: ____________________________________10

7

operations

- electrical: __________________________106 operations at rated load

Output ratings: __________________

RS

stock no. 312-353: relay output,

3A resistor (SPCO)

RS

stock no. 312-369:open collector

transistor,100mA at 30V (SPNO)

Ambient working temperature: ____________________-10˚C to +55˚C
Ambient storage temperature ______________________-25˚C to +65˚C
Weight __________________________________________________112g

+

+

+

+

0.5s

0.5s

set

Figure 7

display

output

time

set

Figure 8

display

output

time

set

Figure 5

display

output

time

set

Figure 6

display

output

time

Circuit

Power

Auto-transformer

Rectifier

circuit