background image

Installation and Operation Manual

page 11

MAN332%1.pm5

3.5 Operation and Functional Test

1. Turn on the UPS by setting the rear panel main switch into position ‘1’ or ‘on’. On the PTM280VA

and PTM420VA models, the UPS will beep and the front panel LED will light. On the PTM650VA

and PTM1KVA models, the UPS will beep and the front panel Normal Mode LED will light.

2. The UPS may be overloaded if the following occurs: On the PTM280VA and PTM420VA models, the

buzzer sounds continuously and the LED is a constant orange colour. On the PTM650VA and

PTM1KVA models, the buzzer sounds continuously and the Overload LED lights. Unplug the least

critical devices, such as a printer etc. to remove the overload condition

Note:

  Backup all unsaved files before you perform the following functional test.

3. To test the backup function, you may unplug the mains lead from the UPS or simply press the Test/

Silence Button on the front panel. During this test, ensure that your equipment operates properly and

without interruption. If you leave your UPS on continuously, it is a good idea to perform a backup

function test at least once a month. The OptiSafe software can be configured to perform automatic

periodic tests.

If you unplug the mains lead, all models will beep once every 4 seconds.  You can press the Test/

Silence Button to silence the alarm.  In addition, on the PTM280VA and PTM420VA models, the LED

will flash on and off.  On the PTM650VA and PTM1KVA models, the Battery Mode LED will light.

Plug the mains lead back in after a few seconds.

If you press the Test/Silence Button, all models wlll beep twice. In addition, on the PTM280VA and

PTM420VA models, the LED will flash twice. On the PTM650VA and PTM1KVA models, the Battery

Mode LED will light. When the test is over, the Normal Mode LED will light.

3.6 Storage Instructions

For extended storage in moderate climates, the battery should be charged for 12 hours every 3 months.

Repeat this every 2 months in high temperature locations. For the PTM280VA and PTM420VA models,

plug the mains lead into the wall socket and turn on the main power switch. For the PTM650VA and

PTM1KVA models, plug in the mains lead. The main power switch does not need to be turned on.

4. User Replaceable Battery

The batteries inside this UPS should last between 3 and 5 years. If you suspect that the batteries are weak,

charge the UPS for at least six (6) hours and then test the UPS again. If the UPS still does not provide

adequate backup time, follow the procedures below to replace the batteries.

4.1 Warning

Please read the following cautions before replacing the batteries.

Except for the battery, the unit contains no user serviceable parts. Repairs should be performed only

by factory trained service personnel.

A battery can generate an electrical shock and high short-circuit current. The following precautions

should be observed when working on batteries.

(1) Remove watches, rings, or metal objects.

(2) Use tools with insulated handles.

Do not dispose of batteries in a fire. The batteries may explode.

Do not open or mutilate batteries. They contain an electrolyte which is toxic and harmful to the skin

and eyes.

Summary of Contents for PTM Series

Page 1: ...PC Power Uninterruptible Power Systems UPS PTM Series MAN 332 Issue 1 Installation and Operation Manual ...

Page 2: ...ENERGY SOURCE BATTERY THE OUTPUT RECEPTACLES MAY BE LIVE EVEN WHEN THE UPS IS NOT CONNECTED TO AN AC SUPPLY For safe and continuous operation of the UPS depends partially on the care taken by users Please observe the following precautions Do not disassemble the UPS Do not attempt to power the UPS from any supply other than a 3 wire grounded source Do not place the UPS near water or in environments...

Page 3: ... Silence Button 6 2 3 Status Indication 6 2 4 User Configurable Settings 7 2 5 Communication Port and Pin Assignments 7 2 6 Data line Surge Suppression 8 3 Installation and Operation 3 1 Unpacking and Inspection 9 3 2 Placement 9 3 3 Determining how much equipment you can connect to your UPS 9 3 4 Powering up and connecting your UPS 10 3 5 Operation and Functional Test 11 3 6 Storage Instructions ...

Page 4: ... UPS provides line conditioning using both buck step down voltage and boost step up voltage functions The line conditioning feature allows the UPS to provide protection over a wider mains voltage range without drawing power from its internal battery 1 3 User Replaceable Battery Design The internal battery is the most critical component in the UPS It has a design life of between 3 5 years With a PC...

Page 5: ... meet specific requirements 1 8 Data Line Surge Protection PTM650VA and PTM1KVA The built in data line surge suppression on the rear panel provides an easy way to protect a network RJ45 or modem RJ11 connection from hazardous spikes 2 UPS Controls 2 1 External Views Front and rear PTM280VA and PTM420VA Phone Data Line Surge Suppression Main switch CircuitBreaker IEC320 Inlet Computer Interface Por...

Page 6: ...UPS fault condition Orange flash once then green Self test activated PTM650VA and PTM1KVA Front Panel LEDs Front Panel LED Condition Boost Mode The UPS is correcting a brownout condition The UPS raises the output voltage by approximately 12 higher than the input voltage without drawing internal battery power Normal Mode The UPS is in normal mode and is providing power to the load The output voltag...

Page 7: ...l if your UPS is protecting a computer system that requires extra time to shut down Delay Audible Alarm in Backup Mode disables the audible alarm during a power failure until the battery power is low This adjustment is useful in areas in which the alarm may be annoying because of frequent short power interruptions DIP Switch Settings PTM280VA 420VA Function Switch Up Switch Down Low Transfer Point...

Page 8: ...in 4 when the battery has less than 2 minutes backup time left PIN 6 User sends a RS232 high level 5 15V for 3 seconds This signal will turn off the UPS until a satisfactory mains voltage is available It can operate only if the UPS is in battery mode This pin is also used as the RS232 received pin RXD PIN 7 Common for pin 6 and pin 9 PIN 8 Not connected PIN 9 RS232 transmitter pin TXD Note 1 Pin 2...

Page 9: ...AVE THE BOX 3 The location should provide adequate air flow around the UPS with 50mm clearance on all sides for proper ventilation 3 3 Determining How Much Equipment You Can Connect to Your UPS 1 Make a list of all equipment that requires protection 2 Each piece of equipment has voltage and current VA ratings printed on the back label Your equipment may have a voltage rating such as 88 264V Since ...

Page 10: ...e outlet of the UPS to your equipment Switch on the computer equipment 2 Power up the UPS by turning on the main switch on the rear panel 3 We recommend that you charge the battery for six 6 hours before use You may use the UPS immediately without charging the battery but the battery charge may be less than 100 The UPS recharges the battery automatically whenever AC power is available Note DO NOT ...

Page 11: ... LED will light Plug the mains lead back in after a few seconds If you press the Test Silence Button all models wlll beep twice In addition on the PTM280VA and PTM420VA models the LED will flash twice On the PTM650VA and PTM1KVA models the Battery Mode LED will light When the test is over the Normal Mode LED will light 3 6 Storage Instructions For extended storage in moderate climates the battery ...

Page 12: ...re is the black wire is 7 Push the new battery into place 8 Re position the battery retaining plate and tighten the four screws 9 Slide the front panel back into place 10 Tighten the two small screws on the bottom of the front panel 4 3 Battery Replacement Procedure for PTM650VA and PTM1KVA Changing the batteries in your UPS is a safe and easy procedure Since the battery is isolated from the AC in...

Page 13: ...Installation and Operation Manual page 13 MAN332 1 pm5 5 Troubleshooting Guide Models PTM280VA PTM420VA Models PTM650VA PTM1KVA ...

Reviews: