ORACLE2 Owner's Manual
5
RSF Woodburning Fireplaces
UNIT DIMENSIONS AND CLEARANCES
23"
11 1/2"
11 1/4"
35 1/4"
38 1/4"
1 1/2"
6 1/2"
18 1/2"
6 1/2"
7"
4 1/4"
29 3/4"
17 3/4"
40"
Refer to Table 1 (G)
for minimum depth
of hearth extension
Refer to Table 1
(B) for minimum
distance of side
wall to the
firebox
opening
Refer to Table 1 (H)
for minimum width
of hearth extension
Non-combustible hearth extension
and spark guard (refer to Table1
(I) and text for particulars)
Refer to
Table 1 (J)
for maximum
mantel shelf
depth
Refer to Table 1 (K)
for minimum mantel
shelf height above
the firebox opening
Figure 1 Dimensions and Clearances
Table 1 Dimensions and Clearances
A
Distance of combustible material from side, back and top standoffs
0" (0,0 mm)
B
Minimum distance of side wall to the side of the firebox opening, this does not
allow to fully open the door. To be able to fully open the door without any
interference from the side wall, it has to be pushed back at least an additional 10".
9" (229
mm)
C Ceiling
clearance:
from the base of the fireplace to the ceiling
Sealed enclosure
Vented enclosure
7'
6'
(2,13 m)
(1,83 m)
D
Minimum chimney height: minimum total chimney height from fireplace top to
below the chimney rain cap (at sea level and no offset)
12' (3,66
m)
E
Maximum chimney height: maximum total chimney height from fireplace top to
below the chimney rain cap
40' (12,19
m)
F
Maximum chimney height supported by the ORACLE2 fireplace
16' (4,88 m)
G
Minimum depth of non-combustible hearth extension: from the front of the
fireplace
16" (406
mm)
H
Minimum width of non-combustible hearth extension: total width, must be
centered on the firebox opening
40" (1,02
m)
I
Minimum width of the spark guard
36" (914 mm)
J
Maximum mantel shelf depth
12" (305 mm)
K
Minimum height of a combustible mantel shelf above the top of the firebox
opening: from the firebox opening to below the combustible mantel (refer to the
"Installation: Mantel" section for particulars)
24" (610
mm)