PEARL 3600 Owner's Manual
19
RSF Woodburning Fireplaces
BENEATH THE HEARTH EXTENSION
If the PEARL3600 is installed on a non-combustible floor,
the cement board and the spark guard specified below are
not required.
Install the spark guard provided (5" x 36" piece of sheet
metal) halfway under the fireplace and halfway under the
hearth extension and centered on the door opening. The
spark guard will extend 2½" beneath the fireplace. This will
make certain that sparks cannot lodge in this area and
start a fire. If necessary, the provided spark guard can be
cut to the minimum width specified in Table 1 (I).
If you are preparing a raised installation, you will need a
custom made spark guard, either a "Z" shaped spark
guard or a right angle spark guard. The Z-shaped spark
guard must be used if the height between the bottom of
the fireplace and the top of the non-combustible flooring of
the hearth extension is less than or equal to 2 ½". The
height of the Z-shaped spark guard must equal the
distance between the floor and the base of the unit and go
under the hearth extension and the fireplace by at least 2½". If the unit is installed higher than 2 ½" from the top of
the flooring, a right-angle spark guard is necessary. The sides of the right-angle spark guard should be at least 2½"
x 2½" and must be covered with non-combustible material. Any custom made spark guard must have the minimum
width specified in Table 1(I), and be installed centered on the door opening.
Flush Hearth
Raised Hearth
Custom Spark Guard
Raised Unit
NOTE
: Custom-made spark guards are site built.
Figure 17 Hearth Requirements
Non-
Combustible
Flooring
Right Angle
Spark Guard
(not provided)
More than 2 1/2"
Non-
Combustible
Flooring
Z-Shaped Spark
Guard (not
provided)
2 1/2" or less
RSF
Fireplace