8
www.repo.eu
Technical Manual - RVL-N Single Wire Loop Box v16.5.2014
Design value of resistance for transversal shear force NRd presented in table 4 is resistance in ultima-
te limit state. The minimum concrete strength in the joint (element/joint concrete) is C25/30 (cylinder
strength 25 MPa, cube strength 30 MPa).
Design values for transversal shear force apply for one pair of RVL wire rope loops (one wire rope loop
on each side of the joint). Distance between wire rope loop pairs must be according to section 6.1.1.
b
s
[mm]
N
Rd
[kN]
≥ 70
3,1
8
4.3 dEsIgn vAluEs of rEsIstAnCE for trAnsvErsAl
shEAr forCE (ACI)
PICTuRE 3 |
Direction of transversal shear force
tAblE 4
| DesigN VaLUes oF ResistaNce FoR tRaNsVeRsaL sHeaR
FoRce FoR wiRe Rope Loops (oNe wiRe Rope Loop oN eacH siDe
oF tHe joiNt)