Real Time Automation, Inc.
60
1-800-249-1612
a)
The number of write messages sent by the gateway
3)
Read Message Count:
a)
-The number of read messages sent by the gateway
4)
Message Error Count:
a)
The number of errors returned by the server in response to messages sent by the gateway
5)
Timeouts:
a)
Total number of Read and Write response messages not received by the gateway
Status Strings
-
These are the values for
All Servers,
or the specific server selected.
1)
Last Error Code:
a)
-Last read request error that the gateway received
Error Code Breakdown
:
"Connection Error":
-Common Errors
0x00030000: Incorrect Rack or Slot number
0x00090000: Cannot connect to server
"Read/Write Error":
-Common Errors
0x00700000: Server doesn't support reading/writing that many points per scanline
0x00900000: Address out of range
0x00C00000: The Data Block (DB) received by the PLC is not valid.
0x01400000: Server security does not permit access with PUT/GET communication from remote
partners. See Protection & Security settings in server to enable.
0x02300000: Read/Write timed out