The BACnet MS/TP master tried to write a priority that was out of range or reserved (Priority
6) and was rejected.
ii)
The BACnet MS/TP master tried to write an arr
ay for an object or property that doesn’t have
an array index.
k)
“Unknown device” –
Gateway is trying to send a message to a device we have not had previous
communication with on the network.
l)
“Timeout” –
BACnet MS/TP message timed out.
m)
“Resources busy” –
BACnet MS/TP message cannot be processed right now.
n)
“Segmentation not supported” –
BACnet MS/TP message is too large to send in one message.
o)
“Service not supported” –
The BACnet MS/TP master tried to perform a service that the gateway
does not support.
p)
“Abort Other” –
BACnet MS/TP message is aborted for an unknown reason.
q)
“Invalid Tag” –
BACnet MS/TP message is not how we expect.
r)
“Unknown” –
BACnet MS/TP message error for an unknown reason.