Variables
- These are the values for
All ASCII,
or the ASCII device selected.
1)
Successful Transmit Count:
a)
Number of messages that the gateway has transmitted to the ASCII device
2)
Successful Receive Count:
a)
Number of complete messages that the gateway has received from the ASCII device
3)
Received due to Length:
a)
Number of messages completed due to the Max Message Length being reached
4)
Received due to Delimiters:
a)
Number of messages completed due to the Start or End Delimiters being seen
5)
Received due to Timeout:
a)
Number of messages completed due to the Receive Character Timeout being reached
6)
Received but Discarded:
a)
Number of messages that are complete but discarded due to the queue being full
b)
Change the Gateway Hold Msg Timeout to be less than what you currently have set
7)
Successful Parsed Messages:
a)
Number of messages that are complete and have been successfully parsed
8)
Failed Parsed Messages:
a)
Number of messages that are complete but have not been parsed successfully
Status Strings
-
These are the values for
All ASCII,
or the ASCII device selected.
1)
Queued Messages:
a)
The gateway will hold up to 20 (configurable) complete messages to send to the other protocol
b)
This will only increment if the Gateway Hold Msg Timeout is non-zero and messages are being
received faster than we can send to the other protocol
2)
Last Parsed Error:
a)
Last parsed error the gateway encountered
Common Error Messages:
1)
Number of Fields Invalid:
The total number of parsed fields is greater than the number of fields the
gateway was expecting
2)
Discard:
The Field has been discarded
3)
Invalid Length for Field:
Number of characters parsed is greater than the number of characters that