Real Time Automation, Inc.
41
1-800-249-1612
27)
Expand the Head Module list under the catalog on the right panel to show the available modules to
insert into the device overview slots.
To insert a module, double click to add it to the next available slot.
NOTE:
When setting up the input/output groups, after the
Save Parameters
button is clicked a
message will appear on how many slots to configure in your controller. Because PROFIBUS doesn’t
care about the ordering you can assign in your controller anyway, so as long there are 3 slots and
the input/output bytes match.
28)
Compile download program to your PLC
Terminology Note and Example:
I addresses refer to Input, Q addresses refer to Output, %B refers to
bytes and %W refers to words. So in this case, you would use %IB1-8, %IB68-195 and %QB1-32 to
access the data to/from the gateway in the PLC.