Real Time Automation, Inc.
51
1-800-249-1612
7)
Solid Red (Fatal Error)
–
The serial port selected on the DF1 Master Configuration page is not
configured.
a)
Verify that DF1 has an enabled port selected. If needed, configure port settings.
Variables
- These are the values for
All Slaves,
or the specific slave selected.
1)
Network Bitmap Status (Displayed in Hex):
a)
Each bit corresponds to a slave. If the bit is set, the slave is connected, otherwise the bit is 0.
b)
Bit 0 corresponds to slave 1 and Bit 4 is for slave 5 and so on.
2)
Read Requests:
a)
Number of DF1 Read Requests that the gateway has sent to the slave device.
3)
Read Responses:
a)
Number of valid DF1 Read Responses that the gateway has received from the slave device.
b)
Note:
This should be equal to the number of Read Requests
4)
Read Timeouts:
a)
Number of times the gateway has reached the timeout period waiting for a read response from
the slave device.
5)
Read Errors:
a)
Number of DF1 Read Errors
6)
Write Requests:
a)
Number of DF1 Write Requests that the gateway has sent to the slave device.
7)
Write Responses:
a)
Number of valid DF1 Write Responses that the gateway has received from the slave device.
b)
Note:
This should be equal to the number of Write Requests
8)
Write Timeouts:
a)
Number of times the gateway has reached the timeout period waiting for a Write Response
from the slave device.
9)
Write Errors:
a)
Number of DF1 write errors
Status Strings
-
These are the values for
All Slaves,
or the specific slave selected.
1)
Last Read Error Code:
a)
Last Read Request Error that the gateway received
2)
Last Write Error Code:
a)
Last Write Request Error that the gateway received