Error Code Breakdown
:
1)
Common Allocation Error Codes - The gateway is sending an error message due to the listed
explanation:
a.
“Connection already in use”
- The gateway tried to open a connection using the supplied
parameters, but failed since an existing connection was already opened.
b.
“More than one guy configuring” –
The gateway is not the only device trying to open a
connection to the Adapter.
c.
“Connection size mismatch” –
One of the assembly sizes configured in the gateway does not
match that Adapter device.
d.
“RPI Values(s) not acceptable” –
The gateway is trying to access the Adapter too quickly.
Increase the RPI value in the gateway.
e.
“Unsupportable RPI” –
The value configured in the gateway for the RPI is not supported in
the Adapter device. Most likely try a larger value.
f.
“Nonexistent instance number” –
The assembly instance configured in the gateway is not
valid for the Adapter.
g.
“Invalid Configuration Path” –
The configuration assembly instance
and/or size doesn’t
match the Adapter.
h.
“Invalid O2T Size” –
The output assemb
ly size doesn’t match
the Adapter.
i.
“Invalid T2O Size” –
The input a
ssembly size doesn’t match the A
dapter.
j.
“Invalid O2T/Consume Path” –
The output assembly instance
and/or size doesn’t match the
Adapter.
k.
“Invalid T2O/Produce Path” –
The input assembly instance and/or size does
n’t match the
Adapter.