Real Time Automation, Inc.
70
1-800-249-1612
Error Code Breakdown
:
1)
Common Allocation Error Codes - The gateway is sending an error message due to the listed
explanation:
2)
“Connection already in use”
- The gateway tried to open a connection using the supplied
parameters but failed since an existing connection was already opened.
3)
“More than one guy configuring” –
The gateway is not the only device trying to open a connection
to the adapter.
4)
“Connection size mismatch” –
One of the assembly sizes configured in the gateway does not match
that adapter device.
5)
“RPI Values(s) not acceptable” –
The gateway is trying to access the adapter too quickly. Increase
the RPI value in the gateway.
6)
“Unsupportable RPI” –
The value configured in the gateway for the RPI is not supported in the
adapter device. Most likely try a larger value.
7)
“Nonexistent instance number” –
The assembly instance configured in the gateway is not valid for
the adapter.
8)
“Invalid Configuration Path” –
The configuration assembly instance and/or size doesn’t match the
adapter.
9)
“Invalid O2T Size” –
The output assembly size doesn’t match the adapter.
10)
“Invalid T2O Size” –
The input assembly size doesn’t match the adapter.
11)
“Invalid O2T/Consume Path” –
The output assembly instance and/or size doesn’t match the adapter.
12)
“Invalid T2O/Produce Path” –
The input assembly instance and/or size doesn’t match the adapter.