For this example: The 460ES is setup as 96bytes in and out.
If the PLC Comm Format is setup for Data
–
Sint, then the connection parameters within the PLC size will
match identical at 96. If the PLC Comm Format is setup for Data
–
Int, then the PLC size needs to be
setup at 48. Since INT has 2 bytes, you’ll need 48 “instances” of 16
-bits which will equal 96 bytes to the
RTA. If PLC Comm Format is setup for Data
–
Dint, then the PLC size needs to be setup at 24.
5)
After you click
OK
, you will be prompted to enter the Requested Pack Interval (RPI). The RPI
minimum value is 20ms.
6)
Click
OK
once more to finish adding the gateway into the PLC.