Real Time Automation, Inc.
58
1-800-249-1612
Example:
This Error Code indicates Code 2, the register was not valid. Other details are:
•
Received the error with FC 15, trying to Force Multiple Coils (WrMCls
–
Write Multiple Coils)
•
N:1, from device 1, the first configured device
•
A:101, Starting address of 101; aka: 000101 or 00101
•
L:32, Multiple registers were trying to write 32 coils.
The Error Code indicates
not valid
, so the starting address was not found, or there were not 32
sequential coils to be written (101 through 132). To solve this, change the starting address, or reduce
the
# of Points
configured.