Expand the Standard node on the right panel to show the available modules to insert (Refer to
the picture in Step 11).
To match the above configuration in the 460 gateway, add one 8-byte input module to slot 1,
one 128-byte input module to slot 2, and one 32-byte output module to slot 11.
Siemens PLC Configuration:
15)
When finished, click the Save and Compile button and then the Download to PLC button.
Terminology Note and Example: I addresses refer to Input, Q address refer to Output, %B refer to bytes
and %W refer to words. So in this case, you would use %IB0-7, %IB128-255 and %QB0-31 to access the
data to/from the gateway in the PLC.