Expand the Module list under the catalog on the right panel to show the available modules to
insert into the device overview slots.
To match the above configuration in the 460 gateway, add one 8-byte input module to slot 1,
one 128-byte input module to slot 2, and one 32-byte output module to slot 11.
TIA Portal Configuration:
To insert a module, just double click to add it to the next available slot.
Terminology Note and Example: I addresses refer to Input, Q address refer to Output, %B refer to
bytes and %W refer to words. So in this case, you would use %IB1-8, %IB68-195 and %QB1-32 to
access the data to/from the gateway in the PLC.