Real Time Automation, Inc.
61
1-800-249-1612
LED Status
- This is the Status for
All Servers
or the specific server selected.
1)
Solid Green (Connected and Running):
a)
The gateway is connected to all S7 servers that are configured and enabled
2)
Flashing Green (Communication not attempted yet):
a)
The gateway hasn't attempted to connect to the S7 server
3)
Flashing Red (Not Connected):
a)
One or more of the servers configured are missing (Nodes Missing)
b)
The Dependency Protocol has Faulted
4)
Flashing Red (Communication not attempted yet):
a)
-No reads are configured, and data needed for writes isn't valid yet
5)
Solid Red (Invalid Configuration):
a)
No devices have been configured
b)
No devices that have been configured are enabled
c)
No devices that have been configured and enabled have scan lines configured
d)
One or more of the servers configured is not on the same subnet as the gateway
6)
Off:
a)
No Power
b)
No Ethernet cable connected
Variables
- These are the values for
All Servers,
or the specific server selected.
1)
Network Bitmap Status (Displayed in Hex):
a)
Each bit corresponds to a server. If the bit is set, the server is connected, otherwise the bit is 0.
b)
Bit 0 corresponds to Server 1 and Bit 4 is for Server 5 and so on.
2)
Write Message Count: