Real Time Automation, Inc.
44
1-800-249-1612
Troubleshooting RSLinx and RSLogix Comms
When attempting to configure the 515RTAENI in
RSLinx I see “unrecognized device” and a yellow
question mark. Why do I see this?
In RSLinx, when using EtherNet/IP, the EDS file for
the 515RTAENI must be installed for RSLinx to
recognize the device type.
Using RSLinx and
RSLogix, pg. 40
When attempting to configure the RSLogix
Controller Communications Comms Path, why
do I
get a 0x10 error after clicking the “Apply”
button.
The 0x10 error indicates that either the serial
baud rates do not match or there is an issue with
the serial cable. Verify that the serial baud rate
configured in the 515RTAENI is the same baud
rate configured in the controller, also verify that
the serial cable is the correct cable and is properly
connected.
Why are The LEDs flashing red when connected
to the 515RTAENI using RSLinx/RSLogix?
In RSLinx if you are using the EtherNet/IP (ETHIP)
driver, you must set the communications path to
the 515RTAENI for connecting a serial only PLC
using Ethernet
.
Using RSLinx and RSLogix, pg.