Modbus Configuration
1)
From the navigation menu, select
Modbus
under Configuration.
TCP/IP Client
2)
Response Timeout: Enter the amount of time the router will wait for the response from
the Modbus TCP/IP Server(s) before calling the message a timeout and closing the
connection.
RTU Slave
3)
Inactivity Timeout
:
Enter the amount of time the router will wait for communication
from the Modbus RTU Master device before it raises an alarm.
a.
Modbus RTU LED will turn red
Map your RTU Slave IDs to TCP/IP Addresses
4)
Number of Devices: Number of mappings.
5)
RTU Slave ID: Slave ID on Modbus RTU. This field must be unique.
6)
TCP/IP Address: Enter the Ethernet TCP/IP address of the Modbus TCP/IP Server.
7)
TCP/IP Port: Enter which port number will be used. Port 80 is not allowed.
8)
TCP/IP Unit ID: Enter the Unit ID for the Modbus TCP/IP Server.
9)
When finished, press the
Save Parameters
button to save the changes made on this
page. If settings have changed, you will be prompted to reboot the router for the
changes to take effect.