78
28.6.
Reinstall the M4SENET-100 card into the Opto22 controller box making sure the
covers and set screws are in place.
28.7.
From the Windows© Toolbar, Select <Start/Programs/Opto22/OptoEnet-
IO/OptoBootP Utility>
28.8.
On the “Opto BootP” Dialog box, Click the “Listen” Pushbutton.
28.9.
After a few seconds, in the dialog box’s data window, a Mac address will be listed
followed by 0.0.0.0 IP Address and a ?.?.?.?. Subnet Mask.
28.10.
Double Click on the 0.0.0.0 field to assign an IP Address
28.11.
Enter “10.192.105.102” for the IP Address and “255.255.255.0” for the Subnet Mask.
Leave the Gateway field 0.0.0.0.
28.12.
Click on the “Send” pushbutton to assign the entered address.
28.13.
The Data Window should now be updated to display a “Yes” under the “Sent”
Column.
28.14.
Click on “Exit” to leave the Opto BootP application.
29.Troubleshooting Windows© Setup of Ethernet Connection
29.1.
Click on the “Start” button
29.2.
Select the “Settings” menu
29.3.
Select the “Control Panel” folder
29.4.
Find, Select and Open the “Network” icon
29.5.
Click on the “Configuration” tab
29.6.
Check to see that the following appear under the listing for “The following network
components are installed:”
(Note: as the actual Ethernet card installed in each furnace may vary, the actual text
may reflect the specific model of Ethernet card actually installed. Below, the protocol
is simply referenced as “… Ethernet …” )
NetBEUI -> … Ethernet …
TCP/IP -> … Ethernet …