background image

 
 

 

11 

 
4  

Maintenance/Service 

 
4.1  

Maintenance intervals  

 
Important!! 

In case of compressor units with V-belt drive, re-tension the  
V-belts and the quick-lock taper bushes of the V-belt pulleys and the fastening screws of the 
discharge silencer after the first two hours of operation. 

 

INSPECTION DURING OPERATION:

 

 
A: 

The  oil  pressure  must  not  drop  below  the  minimum  value  of  0.3  bar,  (normally  1-3 
bar).  When  outside  temperature  is  low  it  may  take  a  few  seconds  before  the  oil 
pressure is visible. 

 
B: 

Check the air filter indicator.  
If the red mark is visible, the air intake filter is soiled and poses a risk of overheating 
and damages. 
 

C: 

The safety valve must open at maximum air pressure.  
This  valve  must  NOT  be  used  as  blow-off  valve.  To  prevent  overheating  in  the 
enclosure the valve at the silo tank must blow off before the compressor valve does. 
(blow-off pressure 2.5 bar) 

 
D: 

Pay attention to any unusual sounds or peculiarities near the installation. 

 
 

WEEKLY INSPECTION:

 

 

ONLY CARRY OUT WHEN INSTALLATION IS COOL AND AT A STANDSTILL 

WITH THE POWER CORD DISCONNECTED OR THE MAIN SWITCH OFF 

 
A: 

Check the level of lubricating oil weekly.  
To achieve longevity of the compressor  it is important the oil level remains between 
the indicated marks on the dip-stick (do not overfill). 
 

B: 

Check the air intake filter at regular intervals. Clean or replace the air filter if 
necessary.  
 * Please note that the air filter is reinserted in the same position (paying attention to 
the front and back of the element). Also check the functioning of the air indicator. 

 
C: 

It  is  important  to  check  the  airflow  and  cleanliness  of  the  fan  louvres  to  prevent 
overheating of the compressor. 

 
 

 

 

Summary of Contents for SiloKing 1100 LS

Page 1: ...INSTRUCTION AND OPERATING MANUAL RTI Compressor unit with electric motor SiloKing 1100 LS These pictures are only examples...

Page 2: ...interference free operation and to achieve longevity Repairs maintenance or conversion work shall only be carried out by authorised trained and qualified personnel that are familiar with the current...

Page 3: ...3 Operating safety conscious 2 4 Safety instructions operator 2 5 Modifications and repairing spare parts 2 6 Modifications unit 3 Commissioning 3 1 Set up 3 2 Operating elements and monitoring gauges...

Page 4: ...ontact details Please mention the PO number when contacting us by phone or mail You will find the PO number on the type plate of the installation Telephone number 0031 544 377050 Fax 0031 544 376499 E...

Page 5: ...oil free Power 52 kW at 2 bar and 2930 rpm Driven by 55 75 kW electrical motor Technical data electrical motor Power 55 kW 400 Volt 75 kW 400 Volt Manufacturer Elsto Elsto Type 250 L 2 A 280 L 4 B Bu...

Page 6: ...sure that the distribution pipes and pipe connections are of the correct size and suitable for the respective operating pressure Install the unit in a place where the ambient air is as cool and clean...

Page 7: ...ection Important Any work on the compressor such as operation and maintenance shall only be carried out by authorised skilled and qualified personnel who are familiar with the applicable safety regula...

Page 8: ...ulations shall be applicable Any special official codes and regulations particularly safety regulations applicable to your operation in view of the local conditions shall be observed likewise In the e...

Page 9: ...air filter 3 3 Start up motor compressor Provide for electrical power connection Check phase circuit direction of rotation control light green ok red set main switch to 2 Press start button green Chec...

Page 10: ...r if necessary see operating instructions for compressor chapter Maintenance Air filter indicator Negative pressure is indicated on the air filter indicator of the compressor unit Important If the 65...

Page 11: ...To prevent overheating in the enclosure the valve at the silo tank must blow off before the compressor valve does blow off pressure 2 5 bar D Pay attention to any unusual sounds or peculiarities near...

Page 12: ...D Check the functioning of the safety valve Air pressure measured at the discharge flange of the compressor may not exceed a maximum gauge pressure of 2 5 Potential pressure loss between compressor an...

Page 13: ...he sound cover only when the compressor is at standstill Caution Burning hazard due to hot machine parts Wear protective gloves 4 2 V belt drive Check the tension of the V belts and asses the wear of...

Page 14: ...Drive speed to high Adjust drive speed Defective non return valve Replace non return valve Safety valve does not blow off Check safety valve Negative pressure gauge reading 65 mbar Suction filter clog...

Reviews: