4.5.2
Terminal Overview
Positioner Terminal
IN +:
Input Signal (+)
IN -:
Input Signal (-)
FG:
Ground
OUT+: Feedback Signal (+)
OUT-: Feedback Signal (-)
4.5.2.1
Ground
4.
Ground must be done before operating the positioner.
5.
Open terminal cover and locate ground terminal plate on the right hand bottom side of the terminal plate. The outer
cable entry is located at outside of the terminal. Please make sure that the resistance is less than 100ohm.
6.
When using external ground, use (+) screw driver to unscrew the ground bolts.
5.
Adjustments
5.1
Auto/Manual Switch (A/M Switch)
Auto/Manual Switch allows the positioner to be functioned as by-pass. If switch is set as Auto, the positioner will operate per
input signal. If switch is set as Manual, the positioner will send supply pressure directly to the actuator.