6
Watchdog Timers:
Programmable
150 ms (RTP3000), 250 ms (RTP3100)
Fixed
1.6 s maximum
Power Requirements:
+5 VDC @ 600 mA.
Termination Module Connectors:
One D-Sub connector, 37 pins for use with the 3055/00
Power Digital Cables. These cables have a diameter of 0.5
inches (1.27 centimeters) with a minimum bend radius of 4.6
inches (11.69 centimeters).
Termination Modules:
3099/17-100 SIL-2 Single Termination Module
3099/18
SIL-3 Dual Termination Module
3099/24-100 SIL-2 Triple Redundant Termination Module
User Replaceable Fuses
Littelfuse type 0665 002.HXSL or
Wickmann type 3741200041
Effect of Incorrect Field Wiring:
Shorted output connections will de-energize and shut down
the output. Open output connections will de-energize and
shut down the output. Both shorts and opens will be
annunciated in the error status word. Reversed output
connections apply reverse voltage to the load.
Termination Module Dimensions:
All Termination Modules are 4.38 inches (11.1 centimeters)
in height and have 3.75 inches (9.5 centimeters) of depth.
The width for each termination module and the compatible
field wiring size is tabulated as following:
Model #
Description
Width
(")
Width
(cm)
Minimum
AWG
Maximum
AWG
3099/17-100
SIL-2 Single Termination Module - 16 channel digital
output, field replaceable fuses
2.99
7.6
30
12
3099/18
SIL-3 Dual Termination Module - 16 channel digital output,
field replaceable fuses
6.38
16.2
30
12
3099/24-100
SIL-2 Triple Termination Module - 16 channel digital
output, field replaceable fuses
4.38
11.1
30
12
Module dimension values are ± 0.05 inches or ± 0.127 centimeters!