23
9:51
9:51
9:51
9:51
9:51
9:51
P15
650 m³/h
P16
650 m³/h
P17
850 m³/h
P18
850 m³/h
P19
1200 m³/h
P28
1200 m³/h
English
MIN.VENT
SUPPLY AIR
MIN.VENT
EXTRACT AIR
BASIC VENT
SUPPLY AIR
BASIC VENT
EXTRACT AIR
SHOCK VENT
SUPPLY AIR
SHOCK VENT
EXTRACT AIR
Continued on page 29!
P 19 Intermittent ventilation supply air / P 28 Intermittent ventilation extract air
The air handling unit runs on closing the external contact to the motion sensor and in Level 3 at the
volume flows set in P19 and P28.
P 15 Minimum ventilation supply air / P 16 Minimum ventilation extract air
The volumetric flow can also be adjusted to „MINIMUM VENTILATION“ (night setback). This param
-
eter is controlled using the timer switch or Level 1 and can be set across the entire air volume range.
P 17 Basic ventilation supply air / P 18 Basic ventilation extract air
The designed volume flow for the „BASIC VENTILATION“ is set in m³/h on the control unit and reg
-
ulated via the parameters P17 and P18 at Level 2 The required duct pressure for „BASIC VENTILA
-
TION“ can be set in Pa with the control unit. The duct pressure can be individually set for supply and
extract air. P 14 External control
www.ruck.eu