P21
P21
P21
P21
P22
P22
P22
P22
English
SUP.AIR TEMP.CON
SUP.AIR TEMP.CON
ETA TEMP.CTRL
ROOMTEMP.CONTROL
HEATING
HEATING
Factory setting
Factory setting
COOLING
HEATING-COOLING
P 22 Heating
The air handling unit is operated in WRG mode and with a
warm water heat register or external electric heat register*.
3-point control or 0-10V
P 22 Cooling
The air handling unit operates in heat recovery mode.
3-point control or 0-10V
P 22 Heating and cooling
Only with option Warm water heating coil or Electric heater*
and option cooling coil.
Heating: 3-point control or 0-10V
Cooling: potential-free contact ON / OFF,
3-point control or 0-10V
P 21 Room, supply or extract air temperature regulation
The room, supply air or extract air temperature regulator compares the air temperature
measured at the temperature sensors with the reference temperature set on the control
unit In the case of heating, a difference between the set-point and actual temperature
causes the controller to increase or reduce the heat output.
P 21 Supply air temperature control
With supply air temperature control, the external heat
source is not taken into account.
Fixed supply air temperature. No other adjustability.
P 21 Extract air temperature control
With extract air regulation, any external heat source in the
room will be taken into account and compensated for by a
correction to the supply air. Fixed extract air temperature.
No other adjustability.
P 21 Room temperature control
With room temperature control, any external heat source
in the room will be taken into account and compensated
for by a correction to the supply air temperature. The room
temperature sensor is in the control unit.
The following parameters are for all types of control: