REVT-05ERV 43
EVT-88 EXHAUST AIR PERFORMANCE RATINGS
AIR
VOLUME
(CFM)
OUTLET
VELOCITY
(FPM)
TOTAL STATIC PRESSURE (In. w.g.)
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
6400
2230
591
2.12
705
2.81
807
3.54
901
4.29
988
5.06 1069 5.85 1145 6.67 1217 7.50
7000
2439
625
2.63
733
3.39
831
4.17
920
4.97 1004 5.80 1082 6.65 1159 7.54 1228 8.40
7600
2648
659
3.22
761
4.04
854
4.87
940
5.73 1021 6.61 1097 7.51 1170 8.43 1239 9.37
8200
2857
692
3.88
789
4.76
879
5.65
961
6.57 1039 7.50
1113 8.45 1184 9.43 1251 10.42
8800
3066
725
4.63
818
5.56
903
6.52
983
7.48 1058 8.47 1130 9.48 1199 10.51
1264 11.55
EVT-10 SUPPLY AIR PERFORMANCE RATINGS
AIR
VOLUME
(CFM)
OUTLET
VELOCITY
(FPM)
TOTAL STATIC PRESSURE (In. w.g.)
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7600
2242
520
2.35
610
3.05
694
3.80
775
4.60
851
5.44
923
6.32
991
7.23 1060 8.17
8200
2419
548
2.85
632
3.58
713
4.37
788
5.21
861
6.09
931
7.01
998
7.97 1061 8.94
8800
2596
575
3.40
655
4.18
731
5.01
803
5.89
873
6.81
941
7.78 1005 8.76 1067 9.78
9400
2773
603
4.03
679
4.85
750
5.72
820
6.63
886
7.59
951
8.59 1013 9.62 1074 10.68
10000
2950
630
4.72
702
5.59
771
6.49
837
7.45
901
8.44
963
9.47 1023 10.55
1082 11.65
EVT-10 EXHAUST AIR PERFORMANCE RATINGS
AIR
VOLUME
(CFM)
OUTLET
VELOCITY
(FPM)
TOTAL STATIC PRESSURE (In. w.g.)
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7600
1788
484
2.06
584
2.86
678
3.75
764
4.69
na
na
na
na
na
na
na
na
8200
1929
507
2.46
602
3.31
691
4.24
774
5.23
851
6.26
na
na
na
na
na
na
8800
2071
530
2.91
620
3.80
704
4.77
784
5.81
859
6.89
na
na
na
na
na
na
9400
2212
554
3.42
638
4.34
719
5.36
795
6.43
868
7.56
937
8.74
na
na
na
na
10000
2353
577
3.97
657
4.94
734
5.99
807
7.11
878
8.29
945
9.51 1009 10.76
na
na
EVT-12 SUPPLY AIR PERFORMANCE RATINGS
AIR
VOLUME
(CFM)
OUTLET
VELOCITY
(FPM)
TOTAL STATIC PRESSURE (In. w.g.)
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8000
2360
523
2.56
610
3.27
692
4.03
770
4.85
845
5.72
916
6.62
984
7.55 1049 8.51
9000
2655
569
3.46
649
4.25
707
4.89
795
5.96
865
6.89
932
7.85
996
8.85 1058 9.88
10000
2950
615
4.56
688
5.41
757
6.31
824
7.25
888
8.24
951
9.26 1011 10.33 1070 11.43
11000
3245
660
5.85
728
6.78
793
7.75
854
8.75
914
9.80
973 10.89 1030 12.01 1086 13.17
12000
3540
703
7.32
768
8.36
828
9.39
886 10.46 942 11.57 997 12.71 1051 13.89 1103 15.11
EVT-12 EXHAUST AIR PERFORMANCE RATINGS
AIR
VOLUME
(CFM)
OUTLET
VELOCITY
(FPM)
TOTAL STATIC PRESSURE (In. w.g.)
0.00
0.50
1.00
1.50
2.00
2.50
3.00
3.50
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
8000
1882
482
2.19
580
3.00
671
3.90
756
4.87
835
5.88
na
na
na
na
na
na
9000
2118
521
2.92
610
3.80
676
4.55
773
5.81
849
6.90
920
8.03
na
na
na
na
10000
2353
560
3.79
641
4.74
719
5.78
793
6.88
864
8.05
932
9.26
997 10.51
na
na
11000
2588
599
4.81
673
5.84
746
6.94
814
8.11
881
9.34
946 10.62
1008 11.95 1065 13.31
12000
2824
624
5.75
705
7.08
771
8.22
837
9.47
900 10.77
961 12.11 1020 13.51 1078 14.95
LOW SPEED
XXXX
An operating point in BOLD TYPE indicates a field furnished drive.
MED SPEED
na
This operating point is outside the efficient operating range of the blower.
HIGH SPEED
XXXX
This operating point exceeds the maximum BHP of the blower motor.
CHART 2 - BLOWER PERFORMANCE
Notes:
1.
This blower data accounts for the pressure drop across the Energy Recovery Wheel and the internal cabinet losses, but does not include the pressure drop for
selected Accessories and Options; which can be found in the corresponding tables and must be added to the system External Static Pressure to determine Total
Static Pressure correct RPM and BHP.
2.
Gross Supply Air Performance Ratings (airflow, pressure, and power) are at Port 2 with Port 1, Port 3 and Port 4 at manufacturers specified static pressures, with
Port 1 and Port 3 equal.
3.
Gross Exhaust Air Performance Ratings (airflow, pressure, and power) are to Port 3 with Port 1, Port 2 and Port 4 at manufacturers specified static pressures, with
Port 2 and Port 4 equal.
4.
Power rating (bhp) does not include drive losses.
5.
Performance ratings do not include the effects of appurtenances in the air stream.
6.
Drives are sized for a minimum of 150% of driven horsepower.
7.
WATTS = 746 x BHP
Summary of Contents for ENERVENT+ EVT-09 Series
Page 30: ...30 REVT 05ERV UNIT WIRING DIAGRAM ...
Page 31: ...REVT 05ERV 31 UNIT WIRING DIAGRAM CONTINUED ...
Page 47: ...REVT 05ERV 47 UNIT WIRING DIAGRAM XVIII WIRING DIAGRAMS ...
Page 48: ...48 REVT 05ERV UNIT WIRING DIAGRAM CONTINUED ...
Page 50: ...50 REVT 05ERV Optional Heat Cool Inputs Optional Pre Post Heat ...
Page 57: ...REVT 05ERV 57 DIAGRAM 15 5 1 MODULATION GAS POST HEAT DIAGRAM 14 2 STAGE GAS POST HEAT ...