background image

10

INSTALLATION

Replacement Units 

To prevent failure of a new unit, the existing line set 

must be correctly sized and cleaned or replaced� 

Care must be exercised that the expansion device 

is not plugged� For new and replacement units, a 

liquid line filter drier must be installed and refrigerant 

tubing must be properly sized� Test the oil for acid� If 

positive, a suction line filter drier is mandatory�

IMPORTANT:

 When replacing an 

R-22 unit with an R-410A unit, either replace 

the line set or ensure that the existing line set is 

thoroughly flushed of any old oil or debris� Flush 

kits are available through aftermarket HVAC stores 

such as Prostock�

Indoor Coil

CAUTION:

 

Only use evaporators 

approved for use on R-410A systems that are 

specifically matched with the outdoor unit per 

the manufacturer’s specification sheets� Use 

of existing R-22 evaporators can introduce 

mineral oil to the R-410A refrigerant, forming two 

different liquids and decreasing oil return to the 

compressor� This can result in compressor failure�

REFER TO INDOOR COIL MANUFACTURER’S 
INSTALLATION INSTRUCTIONS.

IMPORTANT:

 The manufacturer is not 

responsible for the performance and operation of 

a mismatched system or for a match listed with 

another manufacturer’s coil�

NOTICE:

 All (-)PRL units must be 

installed with a matched TXV indoor coil� Refer to 

manufacturer’s outdoor unit specification sheet for 

approved indoor coils�

The thermostatic expansion valve in the 

matching coil is specifically designed to operate 

with R-410A� 

DO NOT use an R-22 TXV or 

evaporator� The existing evaporator must 

be replaced with the factory-specified TXV 

evaporator specifically designed for R-410A�

Location

Do not install the indoor coil in the return duct 

system of a gas or oil furnace� Provide a service 

inlet to the coil for inspection and cleaning� Keep 

the coil pitched toward the drain connection�

CAUTION:

 

When coil is installed 

over a finished ceiling and/or living area, it is 

required that a secondary condensate pan be 

installed under entire unit� Failure to do so can 

result in property damage�

Interconnecting Tubing

All units are factory-charged with R-410A 

refrigerant to cover 15 feet of line set� Adjustment 

of charge may be necessary even if the application 

has exactly 15 feet of line due to other installation 

variables and conditions� All models are supplied 

with service valves� Keep tube ends sealed until 

connection is to be made to prevent system 

contamination� 

Vapor and Liquid Lines

Keep all lines sealed until connection is made�
Make connections at the indoor coil first�
Refer to line size information in the tables on page 

12 for correct size and multipliers to be used to 

determine capacity for various vapor line diameters 

and lengths of run� The losses due to the lines 

being exposed to outdoor conditions are not 

included�

The factory refrigeration charge in the outdoor 

unit is sufficient for the unit and 15 feet [4.6 m] 

of standard size interconnecting liquid and vapor 

lines without a filter drier� For different lengths, 

adjust the charge as indicated below�
1/4" ± .3 oz./foot [6.4 mm ± 8.5 g/.30 m]
5/16" ± .4 oz./foot [7.9 mm ± 11.3 g/.30 m]
3/8" ± .6 oz./foot [9.5 mm ± 17.0 g/.30 m]
1/2" ± 1.2 oz./foot [12.7 mm ± 34.0 g/.30 m]
Add 6 oz� for field-installed filter drier�

Maximum Length of Lines

The maximum length of interconnecting line is 

150 feet [45.7 m]. Always use the shortest length 

possible with a minimum number of bends� 

Additional compressor oil is not required for any 

length up to 150 feet [45.7 m].

NOTICE:

 Excessively long refrigerant 

lines cause loss of equipment capacity�

Tubing

Summary of Contents for ANL-AZ 13 SEER Series

Page 1: ...E INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUSTMENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN F...

Page 2: ...Connections 16 17 Leak Testing 17 Wiring 18 19 Control Wiring 18 Conventional 24 VAC Thermostat Control Wiring 18 Thermostat Wiring Diagrams 18 19 Power Wiring 19 Grounding 19 Start Up 20 24 Start Up...

Page 3: ...essories or devices may adversely affect the operation of the heat pump and may also endanger life and property The manufacturer disclaims any responsibility for such loss or injury resulting from the...

Page 4: ...ther apparent or concealed should be filed immediately with the shipping company Check model number electrical characteristics and accessories to determine if they are correct Check system components...

Page 5: ...rcuit Ampacity Amperes Minimum Amperes Maximum Amperes Face Area Sq Ft m2 No Rows PHYSICAL ELECTRICAL Compressor Fuse or HACR Circuit Breaker Outdoor Coil Weight CFM L s Refrig Per Circuit Oz g Net Lb...

Page 6: ...d proper airflow are critical to achieve rated capacity and efficiency Installation of this product should follow the manufacturer s refrigerant charging and airflow instructions Failure to confirm pr...

Page 7: ...ess 60 152 4 cm above fan discharge unit top to prevent recirculation 6 15 2 cm to coil grille air inlets with 12 30 5 cm minimum recommended Corrosive Environment The metal parts of this unit may be...

Page 8: ...ing a unit on a flat roof use 4 x 4 10 2 cm x 10 2 cm or equivalent stringers positioned to distribute unit weight evenly and prevent noise and vibration Where snowfall is anticipated raise the unit a...

Page 9: ...410A and air should never be mixed in tanks or supply lines or be allowed to accumulate in storage tanks Leak checking should never be done with a mixture of R 410A and air Leak checking can be perfo...

Page 10: ...tall the indoor coil in the return duct system of a gas or oil furnace Provide a service inlet to the coil for inspection and cleaning Keep the coil pitched toward the drain connection CAUTION When co...

Page 11: ...r line length 2 It is recommended to use the smallest liquid line size permitted to minimize the system charge 3 The tables below may be used for sizing lines for a combination of horizontal and verti...

Page 12: ...12 INSTALLATION Interconnecting Tubing cont Tubing...

Page 13: ...13 INSTALLATION Interconnecting Tubing cont Tubing...

Page 14: ...14 INSTALLATION Interconnecting Tubing cont Tubing...

Page 15: ...short as possible with a minimum number of elbows or bends Locations where the tubing will be exposed to mechanical damage should be avoided If it is necessary to use such locations the copper tubing...

Page 16: ...tions Indoor coils have only a holding charge of dry nitrogen Keep all tube ends sealed until connections are to be made Use type L copper refrigeration tubing Braze the connections with the following...

Page 17: ...oxygen to purge lines or pressurize system for leak test Oxygen reacts violently with oil which can cause an explosion resulting in severe personal injury or death Pressurize line set and coil throug...

Page 18: ...RE CONNECTION YL BR X X FOR TYPICAL ELECTRIC HEAT W BL R W BK G BK YL BR PU BR BROWN WIRE R RED WIRE YL YELLOW WIRE W BK WHITE WIRE WITH BLACK STRIPE G BK GREEN WIRE WITH BLACK STRIPE PU PURPLE WIRE N...

Page 19: ...ed to the bottom of the control box Connect power wiring to line voltage lugs located in the outdoor unit electrical box See wiring diagram attached to unit access panel Check all electrical connectio...

Page 20: ...ng space These simple mathematical formulas can be used to determine the CFM in a residential or light commercial system Electric resistance heaters can use CFM volts x amps x 3 413 SHC x temp rise Ga...

Page 21: ...may lead to false readings because of pressure drop through the fittings After adequate evacuation open both service valves by removing both brass service valve caps with an adjustable wrench Insert a...

Page 22: ...d valve small valve and the service port on the suction line between the reversing valve and compressor are to be used Confirm ID Airflow and Coils Are Clean Confirm adequate indoor supply airflow pri...

Page 23: ...conditions ONLY Cooling Mode ONLY 55 F 12 8 C outdoor dry bulb and above Heating Mode ONLY Between 40 F 4 4 C and 60 F 15 6 C outdoor dry bulb 3 Locate and note the design pressures The correct liqui...

Page 24: ...om pressure ports then replace the pressure port caps and tighten adequately to seal caps Do not overtighten Replace the service valve caps finger tight and then tighten with an open end wrench adequa...

Page 25: ...re control LPC is an automatic reset which opens near 15 PSIG and closes near 40 PSIG NOTICE HPC and LPC are monitored by the Comfort Control2 System See Comfort Control2 SystemTM on page 26 CAUTION T...

Page 26: ...off due to a power failure or thermostat operation this control keeps it off at least 5 minutes which allows the system pressure to equalize thus not damaging the compressor or blowing fuses on start...

Page 27: ...ve Closed Restricted Indoor Metering Device Restricted Filter Drier Dirty Outdoor Coil Inoperative Outdoor Fan Overcharge Recirculation of Outdoor Air Noncondensibles Higher Than Ambient Air Entering...

Page 28: ...ton Charge per procedure attached to unit service panel Recover refrigerant Evacuate and recharge Add filter drier Compressor short cycles Incorrect voltage Defective overload protector Refrigerant un...

Page 29: ...and complete diagnosis High line voltage Power company problem Have problem corrected High head pressure Overcharge Check system charge Dirty heat pump coil Clean coil Faulty or wrong size heat pump...

Page 30: ...k for correct ohms Voltage present on line side of com pressor contactor only Thermostat Check for control voltage to contactor coil Compressor control circuit High pressure switch Low pressure switch...

Page 31: ...REMEDY Compressor failures Line tubing too large Reduce pipe size to improve oil return Low suction pressure Low charge Check system charge Refrigerant leaks Repair and recharge Cold noisy compressor...

Page 32: ...nal equalizer line restriction Undersized TEV Replace with correct valve Loss of charge from power head sensing bulb Replace power head or complete TEV Charge migration from sensing bulb to power head...

Page 33: ...l Ensure blower is moving proper air CFM Remove Correct any airflow restriction Superheat and suction pressure fluctuate valve is hunting Expansion valve is oversized Install correct TEV Sensing bulb...

Page 34: ...High Low High High Undercharge Low Low High Low Low Liquid Restriction Drier Low Low High High Low Low Indoor Airflow Low Low Low Low Low Dirty Outdoor Coil High High Low Low High Low Outdoor Ambient...

Page 35: ...35 For Single Phase Models WIRING DIAGRAMS Wiring Diagrams...

Page 36: ...36 WIRING DIAGRAMS For Three Phase Models Wiring Diagrams...

Page 37: ...37 Wiring Diagrams APM 018 WITH ECM FAN MOTOR WIRING DIAGRAMS...

Page 38: ...38 NOTES...

Page 39: ...39 NOTES...

Page 40: ...40 NOTES...

Reviews: