INSTALLATION
Interconnecting Tubing (cont�)
Outdoor Unit Installed Above
or Below Indoor Coil
Use the following guidelines when installing the unit:
1� Expansion Valve Coil:
a� The vertical separation cannot exceed the
value in the tables below�
b� No changes are required for expansion valve
coils due to vertical separation or line length�
2� It is recommended to use the smallest liquid line
size permitted to minimize the system charge�
3� The tables below may be used for sizing lines
for a combination of horizontal and vertical runs�
VAPOR LINE SIZING
Allowed suction line size is determined by total line length based on oil return� Liquid size determines total line length and vertical separa-
tion� After selecting allowed suction line by outdoor unit position, see the liquid line chart for allowable vertical height and total line length�