22
START-UP
Checking Refrigerant Charge
Charge for all systems should be checked against
the Charging Chart inside the access panel cover�
WARNING:
The top of the scroll
compressor shell is hot� Touching the compressor
top may result in serious personal injury�
IMPORTANT:
Use factory-approved
charging method as outlined on the next page to
ensure proper system charge�
NOTICE:
The optimum refrigerant charge
for any outdoor unit matched with a CFL/CFM/H*L
indoor coil/air handler is affected by the
application� Therefore, charging data has
been developed to assist the field technician
in optimizing the charge for all mounting
configurations (UF – Upflow, DF – Downflow,
LH – Left-Hand Discharge, and RH – Right-Hand
Discharge)� Refer to the charging chart inside the
access panel cover on the unit and choose the
appropriate column for the specific application
being installed or serviced� New installations
utilizing either a CFL/CFM indoor coil installed on a
gas furnace or an H*L air handler in the downflow
or horizontal right-hand discharge may require
removal of refrigerant since the factory charge
could result in an overcharge condition�
Charging Units With R-410A
Refrigerant
CAUTION:
R-410A pressures are
approximately 60% higher (1�6 times) than R-22
pressures� Use appropriate care when using this
refrigerant� Failure to exercise care may result in
equipment damage or personal injury�
Charge for all systems should be checked against
the Charging Chart inside the access panel cover�
IMPORTANT:
Do not operate the
compressor without charge in the system�
Addition of R-410A will raise high-side pressures
(liquid and discharge)�
NOTICE:
System maintenance is to be
performed by a qualified and certified technician�
The following method is used for charging systems
in the cooling and heating mode� All steps listed
should be performed to ensure proper charge has
been set� For measuring pressures, the service
valve port on the liquid valve (small valve) and
the service port on the suction line between the
reversing valve and compressor are to be used�
Confirm ID Airflow and Coils
Are Clean
Confirm adequate indoor supply airflow prior to
starting the system� See the Technical Specification
Sheet for rated airflow for each ID/OD unit match�
Air filter(s) and coils (indoor and outdoor) are to be
clean and free of frost prior to starting the system�
Supply airflow must be between 375 and 450 cfm
per rated cooling ton prior to adjusting system
charge� If a humidification system is installed,
disengage it from operation prior to charge
adjustment� Refer to the “Checking Airflow” section
of this manual for further instruction�
NOTICE:
Verify system components
are matched according to the outdoor unit
Specification Sheet�
Measurement Device Setup
1� With an R-410A gauge set, attach the high-
pressure hose to the access fitting on the liquid
line (small) service valve at the OD unit�
2� Attach the low-pressure hose to the common
suction port connected to the common suction
line between the reversing valve and compressor�
3. Attach a temperature probe within 6" [15.2 cm]
outside of the unit on the copper liquid line
(small line)� For more accurate measurements,
clean the copper line prior to measurement and
use a calibrated clamp-on temperature probe or
an insulated surface thermocouple�
Charging by Weight
NOTICE:
Adjust the system charge by
weight for the straight length of the refrigerant line set�
For a new installation, evacuation of inter-
connecting tubing and indoor coil is adequate;
otherwise, evacuate the entire system� Use the
factory charge shown in “Electrical and Physical
Data” on page 5 of these instructions or on the
unit data plate� Note that the charge value includes
charge required for 15 ft. [4.6 m] of standard-size
interconnecting liquid line without a filter drier�
Calculate actual charge required with installed
liquid line size and length using:
1/4" [6.4 mm] O.D. = .3 oz./ft. [8.5 g/.30 m]
5/16" [7.9 mm] O.D. = .4 oz./ft. [11.3 g/.30 m]
3/8" [9.5 mm] O.D. = .6 oz./ft. [17.0 g/.30 m]
1/2" [12.7 mm] O.D. = 1.2 oz./ft. [34.0 g/.30 m]
Add 6 oz� for field-installed filter drier�
Refrigerant
Summary of Contents for ANL-AZ 13 SEER Series
Page 12: ...12 INSTALLATION Interconnecting Tubing cont Tubing...
Page 13: ...13 INSTALLATION Interconnecting Tubing cont Tubing...
Page 14: ...14 INSTALLATION Interconnecting Tubing cont Tubing...
Page 35: ...35 For Single Phase Models WIRING DIAGRAMS Wiring Diagrams...
Page 36: ...36 WIRING DIAGRAMS For Three Phase Models Wiring Diagrams...
Page 37: ...37 Wiring Diagrams APM 018 WITH ECM FAN MOTOR WIRING DIAGRAMS...
Page 38: ...38 NOTES...
Page 39: ...39 NOTES...
Page 40: ...40 NOTES...