background image

23

With an accurate scale (+/– 1 oz. [28.3 g]) or 

volumetric charging device, adjust charge 

difference between that shown on the unit data 

plate and that calculated for the new system 

installation� If the entire system has been 

evacuated, add the total calculated charge�

IMPORTANT:

 Charging by weight is  

not always accurate since the application can 

affect the optimum refrigerant charge� Charging by 

weight is considered a starting point ONLY� Always 

check the charge by using the Charging Chart 

and adjust as necessary� CHARGING BY LIQUID 

SUBCOOLING MUST BE USED FOR FINAL 

CHARGE ADJUSTMENT�

With thermostat in the “Off” position, turn on the 

power to the furnace or air handler and the heat 

pump� Start the heat pump and the furnace or air 

handler with the thermostat� Verify that the outdoor 

unit is operating in second stage and the indoor 

air mover is delivering the second-stage airflow for 

the system size�

Gross Charging by Pressures

1� Following airflow verification and charge weigh-

in, run the unit for a minimum of 15 minutes 

prior to noting pressures and temperature�

IMPORTANT:

 Indoor conditions 

as measured at the indoor coil must be within 

2°F [1.1°C] of the following during gross charge 

(pressure) evaluation:

Cooling Mode: 80°F [26.7°C] Dry Bulb
Heating Mode: 70°F [21.1°C] Dry Bulb

NOTICE:

 If the Indoor temperature is above  

or below this range, run the system to bring the 

temperature down or run the electric heat/furnace 

to bring the temperature within this range� System 

pressure values provided in the Charging Chart for 

outdoor dry bulbs corresponding to conditions outside 

of these ranges are provided as reference ONLY� 

2� Note the Outdoor Dry Bulb Temperature, 

ODDB° = _____°F [_____°C]� Unit charging is 

recommended under the following outdoor 

conditions ONLY:
Cooling Mode ONLY: 55°F [12.8°C] outdoor dry 

bulb and above
Heating Mode ONLY: Between 40°F [4.4°C] and 

60°F [15.6°C] outdoor dry bulb

3� Locate and note the design pressures� The 

correct liquid and vapor pressures are found at 

the intersection of the installed system and the 

outdoor ambient temperature on the Charging 

Chart located inside the access panel cover� 
Liquid Pressure: = ______psig; Vapor Pressure = 

______psig

NOTICE:

 The refrigerant pressures provided 

are for gross charge check ONLY� These pressure 

values are typical, but may vary due to application� 

Evaporator load (indoor coil in cooling mode/outdoor 

coil in heating mode) will cause pressures to deviate� 

Note that all systems have unique pressure curves� 

The variation in the slope and value is determined 

by the component selection for that indoor/outdoor 

matched system� The variation from system to 

system seen in the table is normal� The values listed 

are for the applicable indoor coil match ONLY!
4� If the measured liquid pressure is below the 

listed requirement for the given outdoor and 

indoor conditions, add charge� If the measured 

liquid pressure is above the listed requirement 

for the given outdoor and indoor conditions, 

remove charge� 

Final Charge by Subcooling

1� After gross charging, note the designed 

subcooling value� The correct subcooling value 

is found at the intersection of the installed 

system and the outdoor ambient temperature 

on the Charging Chart located inside the access 

panel cover� 
SC° from Charging Chart = _____°F [_____°C].

IMPORTANT:

 Indoor conditions as 

measured at the indoor coil are required to be 

between 70°F [21.1°C] and 80°F [26.7°C] dry 

bulb for fine-tuned unit charge adjustment� Unit 

charging is recommended under the following 

outdoor conditions ONLY:

Cooling Mode ONLY: 55°F [12.8°C] outdoor dry 

bulb and above
Heating Mode ONLY: Between 40°F [4.4°C] and 

60°F [15.6°C] outdoor dry bulb

START-UP

Checking Refrigerant Charge (cont�)

Refrigerant

Summary of Contents for ANL-AZ 13 SEER Series

Page 1: ...E INSTRUCTIONS THOROUGHLY BEFORE ATTEMPTING INSTALLATION OR OPERATION FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUSTMENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN F...

Page 2: ...Connections 16 17 Leak Testing 17 Wiring 18 19 Control Wiring 18 Conventional 24 VAC Thermostat Control Wiring 18 Thermostat Wiring Diagrams 18 19 Power Wiring 19 Grounding 19 Start Up 20 24 Start Up...

Page 3: ...essories or devices may adversely affect the operation of the heat pump and may also endanger life and property The manufacturer disclaims any responsibility for such loss or injury resulting from the...

Page 4: ...ther apparent or concealed should be filed immediately with the shipping company Check model number electrical characteristics and accessories to determine if they are correct Check system components...

Page 5: ...rcuit Ampacity Amperes Minimum Amperes Maximum Amperes Face Area Sq Ft m2 No Rows PHYSICAL ELECTRICAL Compressor Fuse or HACR Circuit Breaker Outdoor Coil Weight CFM L s Refrig Per Circuit Oz g Net Lb...

Page 6: ...d proper airflow are critical to achieve rated capacity and efficiency Installation of this product should follow the manufacturer s refrigerant charging and airflow instructions Failure to confirm pr...

Page 7: ...ess 60 152 4 cm above fan discharge unit top to prevent recirculation 6 15 2 cm to coil grille air inlets with 12 30 5 cm minimum recommended Corrosive Environment The metal parts of this unit may be...

Page 8: ...ing a unit on a flat roof use 4 x 4 10 2 cm x 10 2 cm or equivalent stringers positioned to distribute unit weight evenly and prevent noise and vibration Where snowfall is anticipated raise the unit a...

Page 9: ...410A and air should never be mixed in tanks or supply lines or be allowed to accumulate in storage tanks Leak checking should never be done with a mixture of R 410A and air Leak checking can be perfo...

Page 10: ...tall the indoor coil in the return duct system of a gas or oil furnace Provide a service inlet to the coil for inspection and cleaning Keep the coil pitched toward the drain connection CAUTION When co...

Page 11: ...r line length 2 It is recommended to use the smallest liquid line size permitted to minimize the system charge 3 The tables below may be used for sizing lines for a combination of horizontal and verti...

Page 12: ...12 INSTALLATION Interconnecting Tubing cont Tubing...

Page 13: ...13 INSTALLATION Interconnecting Tubing cont Tubing...

Page 14: ...14 INSTALLATION Interconnecting Tubing cont Tubing...

Page 15: ...short as possible with a minimum number of elbows or bends Locations where the tubing will be exposed to mechanical damage should be avoided If it is necessary to use such locations the copper tubing...

Page 16: ...tions Indoor coils have only a holding charge of dry nitrogen Keep all tube ends sealed until connections are to be made Use type L copper refrigeration tubing Braze the connections with the following...

Page 17: ...oxygen to purge lines or pressurize system for leak test Oxygen reacts violently with oil which can cause an explosion resulting in severe personal injury or death Pressurize line set and coil throug...

Page 18: ...RE CONNECTION YL BR X X FOR TYPICAL ELECTRIC HEAT W BL R W BK G BK YL BR PU BR BROWN WIRE R RED WIRE YL YELLOW WIRE W BK WHITE WIRE WITH BLACK STRIPE G BK GREEN WIRE WITH BLACK STRIPE PU PURPLE WIRE N...

Page 19: ...ed to the bottom of the control box Connect power wiring to line voltage lugs located in the outdoor unit electrical box See wiring diagram attached to unit access panel Check all electrical connectio...

Page 20: ...ng space These simple mathematical formulas can be used to determine the CFM in a residential or light commercial system Electric resistance heaters can use CFM volts x amps x 3 413 SHC x temp rise Ga...

Page 21: ...may lead to false readings because of pressure drop through the fittings After adequate evacuation open both service valves by removing both brass service valve caps with an adjustable wrench Insert a...

Page 22: ...d valve small valve and the service port on the suction line between the reversing valve and compressor are to be used Confirm ID Airflow and Coils Are Clean Confirm adequate indoor supply airflow pri...

Page 23: ...conditions ONLY Cooling Mode ONLY 55 F 12 8 C outdoor dry bulb and above Heating Mode ONLY Between 40 F 4 4 C and 60 F 15 6 C outdoor dry bulb 3 Locate and note the design pressures The correct liqui...

Page 24: ...om pressure ports then replace the pressure port caps and tighten adequately to seal caps Do not overtighten Replace the service valve caps finger tight and then tighten with an open end wrench adequa...

Page 25: ...re control LPC is an automatic reset which opens near 15 PSIG and closes near 40 PSIG NOTICE HPC and LPC are monitored by the Comfort Control2 System See Comfort Control2 SystemTM on page 26 CAUTION T...

Page 26: ...off due to a power failure or thermostat operation this control keeps it off at least 5 minutes which allows the system pressure to equalize thus not damaging the compressor or blowing fuses on start...

Page 27: ...ve Closed Restricted Indoor Metering Device Restricted Filter Drier Dirty Outdoor Coil Inoperative Outdoor Fan Overcharge Recirculation of Outdoor Air Noncondensibles Higher Than Ambient Air Entering...

Page 28: ...ton Charge per procedure attached to unit service panel Recover refrigerant Evacuate and recharge Add filter drier Compressor short cycles Incorrect voltage Defective overload protector Refrigerant un...

Page 29: ...and complete diagnosis High line voltage Power company problem Have problem corrected High head pressure Overcharge Check system charge Dirty heat pump coil Clean coil Faulty or wrong size heat pump...

Page 30: ...k for correct ohms Voltage present on line side of com pressor contactor only Thermostat Check for control voltage to contactor coil Compressor control circuit High pressure switch Low pressure switch...

Page 31: ...REMEDY Compressor failures Line tubing too large Reduce pipe size to improve oil return Low suction pressure Low charge Check system charge Refrigerant leaks Repair and recharge Cold noisy compressor...

Page 32: ...nal equalizer line restriction Undersized TEV Replace with correct valve Loss of charge from power head sensing bulb Replace power head or complete TEV Charge migration from sensing bulb to power head...

Page 33: ...l Ensure blower is moving proper air CFM Remove Correct any airflow restriction Superheat and suction pressure fluctuate valve is hunting Expansion valve is oversized Install correct TEV Sensing bulb...

Page 34: ...High Low High High Undercharge Low Low High Low Low Liquid Restriction Drier Low Low High High Low Low Indoor Airflow Low Low Low Low Low Dirty Outdoor Coil High High Low Low High Low Outdoor Ambient...

Page 35: ...35 For Single Phase Models WIRING DIAGRAMS Wiring Diagrams...

Page 36: ...36 WIRING DIAGRAMS For Three Phase Models Wiring Diagrams...

Page 37: ...37 Wiring Diagrams APM 018 WITH ECM FAN MOTOR WIRING DIAGRAMS...

Page 38: ...38 NOTES...

Page 39: ...39 NOTES...

Page 40: ...40 NOTES...

Reviews: