background image

A. Indoor blower contactor is energized through thermostat contact (G).

B. Compressor contactors are energized through thermostat contacts (Y1) and (Y2). A

5 minute short cycle delay is standard on this unit. Compressor will start immediate-
ly if test pins on the defrost board are shorted and released.

C. Reversing valve is energized in the heating mode through thermostat contact (B).

D. Economizer  enthalpy  control  (if  installed)  is  electrically  bypassed  with  the  heat

pump control relay during heating operation.

E. Should the heat requirement be more than the heat pump can supply, a portion of

the  electric  heat  accessory  (if  supplied)  is  energized  through  thermostat  contact
(W3).

F. The  system  will  continue  in  heating  operation  as  long  as  all  safety  controls  are

closed, until the thermostat is satisfied.

G. The unit will function in a defrost mode, reversing the refrigerant cycle to cooling and

energizing the electric heat (if supplied) as required through the defrost and electric
heat relays.

H. If the refrigerant system becomes inoperable during a need for heating, the thermo-

stat may be set to emergency heat which will energize the electric heat (if supplied).

At initial start-up or after extended shutdown periods, make sure the crankcase heater
is energized for at least 12 hours before the compressor is started.

XVIII. AUXILIARY HEAT

The amount of auxiliary heat required depends on the heat loss of the structure to be
heated  and  the  capacity  of  the  heat  pump.  It  is  good  practice  to  install  strip  heat  to
maintain at least 60°F indoor temperatures in case of compressor failure. The auxiliary
heat is energized by the second stage of the thermostat. The amount of electric heat
that is allowed to come on, as determined by the output of the heat pump, may be con-
trolled by an outdoor thermostat.

XIX. DEMAND DEFROST CONTROL AND
HIGH/LOW PRESSURE CONTROLS

The  demand  defrost  control  monitors  the  outdoor  ambient  temperature,  outdoor
coil temperature and the compressor run time to determine when a defrost cycle
is required.

Enhanced Feature Demand Defrost Control: This defrost control has high and
low pressure control inputs with unique pressure switch logic built into the micro-
processor  to  provide  compressor  and  system  protection  without  nuisance  lock-
outs. The control cycles the compressor off for 30 seconds at the beginning and
the end of the defrost cycle to eliminate the increased compressor noise caused
by  rapidly  changing  system  pressures  when  the  reversing  valve  switches.  See
next page for diagnostic flash codes and sensor resistance values at various tem-
peratures.

DEFROST INITIATION

A defrost will be initiated when the three conditions below are satisfied:

1.

The outdoor coil temperature is below 35°F as measured by a good coil sen-
sor,

2.

The  compressor  has  operated  for  at  least  34  minutes  with  the  outdoor  coil
temperature below 35°F and

3.

The measured difference between the ambient temperature and the outdoor
coil  temperature  is  greater  than  the  calculated  difference  determined  by  the
defrost control microprocessor.

ONLY  ELECTRIC  HEATER  KITS  SUP-
PLIED  BY  THIS  MANUFACTURER  AS
DESCRIBED  IN  THIS  PUBLICATION
HAVE BEEN DESIGNED, TESTED, AND
EVALUATED  BY  A  NATIONALLY  REC-
OGNIZED  SAFETY  TESTING  AGENCY
FOR USE WITH THIS UNIT. USE OF ANY
OTHER  MANUFACTURED  ELECTRIC
HEATERS  INSTALLED  WITHIN  THIS
UNIT  MAY  CAUSE  HAZARDOUS  CON-
DITIONS  RESULTING  IN  PROPERTY
DAMAGE,  FIRE,  BODILY  INJURY  OR
DEATH.

WARNING

!

ONLY  ELECTRIC  HEATER  KITS  SUPPLIED  BY  THIS  MANUFACTURER  AS
DESCRIBED  IN THIS  PUBLICATION  HAVE  BEEN  DESIGNED, TESTED,  AND
EVALUATED  BY  A  NATIONALLY  RECOGNIZED  SAFETY TESTING  AGENCY
FOR USE WITH THIS UNIT. USE OF ANY OTHER MANUFACTURED ELECTRIC
HEATERS INSTALLED WITHIN THIS UNIT MAY CAUSE HAZARDOUS CONDI-
TIONS  RESULTING  IN  PROPERTY  DAMAGE,  FIRE,  BODILY  INJURY  OR
DEATH.

WARNING

!

20

Summary of Contents for RJNL-B SERIES

Page 1: ...f r i h RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION DO NOT DESTROY THIS MANUAL PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN WARNING T...

Page 2: ...earances 13 Rooftop Installation 13 Ductwork 14 Filters 14 Cover Panel Installation Conversion Procedure 15 Condensate Drain 15 Condensate Drain Outdoor Coil 15 Electrical Wiring 15 Power Wiring 15 Co...

Page 3: ...he cabinet fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit 2 Regular cleaning and waxing of the cabinet with a good automobile polish w...

Page 4: ...ssure of R 410A is approximately 60 1 6 times greater than R 22 Recovery and recycle equipment pumps hoses and the like need to have design pressure ratings appropriate for R 410A Manifold sets need t...

Page 5: ...gned for R 410A 4 Tools Required For Installing Servicing R 410A Models Manifold Sets Up to 800 PSIG High side Up to 250 PSIG Low Side 550 PSIG Low Side Retard Manifold Hoses Service Pressure Rating o...

Page 6: ...RICAL ENTRY LOW VOLTAGE ELECTRICAL ENTRY POWER C O N D E N S E R C O I L SUPPLY AIR RETURN AIR FIGURE 1 UNIT DIMENSIONS BOTTOM VIEW FIGURE 2 UNIT DIMENSIONS BOTTOM VIEW ST A1125 02B ST A1125 09B Typic...

Page 7: ...125 03 ST A1125 08B OUTDOOR FAN 2 2 OUTDOOR FAN 1 1 3 OUTDOOR FAN 3 6 5 4 OUTDOOR FAN 5 OUTDOOR FAN 4 OUTDOOR FAN 6 OUTDOOR COIL SUPPLY AIR FILTER RACK RETURN COMPARTMENT COMPRESSOR 2 FIGURE 5 COMPONE...

Page 8: ...COMPRESSOR ACCESS OUTDOOR FANS FIGURE 7 UNIT DIMENSIONS COMPONENT ACCESS ST A1125 01B 1 2 3 4 5 6 OUTDOOR FAN 4 OUTDOOR FAN 1 OUTDOOR FAN 5 OUTDOOR FAN 6 OUTDOOR FAN 3 OUTDOOR FAN 2 CONTROL COMPARTMEN...

Page 9: ...trol TX Valves TX Valves TX Valves TX Valves Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm 0 375 9 5 0 375 9 5 0 375 9 5 0 375 9 5 Face...

Page 10: ...m 53 3 4 95 53 3 4 95 Rows FPI FPcm 1 22 9 1 22 9 Refrigerant Control TX Valves TX Valves Indoor Coil Fin Type Louvered Louvered Tube Type Rifled Rifled Tube Size in mm 0 375 9 5 0 375 9 5 Face Area...

Page 11: ...30 90 90 90 90 45 45 30 35 100 100 100 100 45 50 35 35 2 2 2 2 2 2 200 230 200 230 460 460 575 575 3 3 3 3 3 3 3450 3450 3450 3450 3450 3450 7 7 7 7 7 7 25 25 25 25 12 2 12 2 9 9 164 164 164 164 100...

Page 12: ...vibration slab should not be connected to building structure 3 The location of the unit should be such as to provide proper access for inspection and servicing 4 Locate unit where operating sounds wi...

Page 13: ...embly see Roofcurb Installation Instruc tions 4 If the roofcurb is not used provisions for disposing of con densate water runoff must be provided 5 The unit should be placed on a solid and level roofc...

Page 14: ...or crawl space should be insulated with at least 2 of insulation with vapor barrier One half to 1 thickness of insulation is usually sufficient for ductwork inside the air conditioned space Balancing...

Page 15: ...e of this unit some of the condensate line joints should assembled for easy removal and cleaning Use a thin layer of Teflon tape or paste on drain pan connections and install only hand tight Do not ov...

Page 16: ...screws previously removed d Connect the unit contactor wires 1L1 1L2 1L3 to the compressor fuse block on the heater kit e Re install the power entry panel run conduit and the proper size field wiring...

Page 17: ...STAT WIRING IN THIS CHASE TO CONTROL BOARD 2 CAP PLUGS BASE CONTROL ENTRY BASE POWER ENTRY FIGURE 17 THERMOSTAT CONNECTIONS DIAGRAMS R Y1 Y2 G C TERMINAL BLOCK ST A1125 36 00 ONLY USED ON DUAL FUEL OR...

Page 18: ...7 723 2748 744 2877 764 3003 785 3124 804 3265 823 3410 842 3559 860 3710 878 3865 895 4024 912 4185 929 4350 7200 3398 570 1897 595 2042 619 2185 643 2327 666 2466 689 2602 711 2737 732 2870 753 3000...

Page 19: ...ate_________________________________________ 8 Turn thermostat system switch to HEAT Unit compressors should stop Raise temper ature setting to above room temperature Unit should run in heating mode a...

Page 20: ...MAND DEFROST CONTROL AND HIGH LOW PRESSURE CONTROLS The demand defrost control monitors the outdoor ambient temperature outdoor coil temperature and the compressor run time to determine when a defrost...

Page 21: ...lly If not check the coil and ambient temperature sensor resistances using the sensor temperature vs resistance table at the end of this section Immerse the sensor in water and measure the resistance...

Page 22: ...he unit or by shorting the two defrost control pins together ENHANCED FEATURE DEFROST CONTROL DIAGNOSTIC CODES SENSOR TEMPERATURE VS RESISTANCE TABLE REPLACEMENT PARTS Contact your local distributor f...

Page 23: ...66 295 300 350 300 350 188 217 200 225 78 78 100 100 100 100 B180CM No Heat 81 81 100 100 100 100 81 81 100 100 100 100 CE20C 1 14 4 19 2 49 13 65 5 40 46 2 131 139 150 175 150 175 50 58 50 60 81 81 1...

Page 24: ...ier Incorrect voltage At compressor terminals voltage must be within 10 of rating plate volts when unit is operating Compressor short cycles Incorrect voltage At compressor terminals voltage must be 1...

Page 25: ...25...

Page 26: ...26 NOTE 15 TON UNIT DOES NOT HAVE OFM 2 5...

Page 27: ...URE PSIG INDOOR AMBIENT F DB SUCTION PRESSURE PSIG 115 105 95 85 75 65 55 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 100 120 140 160 180 200 220 60 65 70 75 80 240 260...

Page 28: ...28 CM 0913 RJNL SERIES 15 TON...

Reviews: