background image

21

DEFROST TERMINATION

Once a defrost is initiated, the defrost will continue until fourteen minutes has elapsed
or the coil temperature has reached the selected termination temperature. The facto-
ry setting is 70°F but can be changed to 50°F, 60°F, or 80°F by relocating the jumper
on the control board.

TEMPERATURE SENSORS

The  coil  sensor  is  located  on  the  outdoor  coil  near  the  point  fed  by  the  distribution
tubes  from  the  expansion  device,  on  the  top  most  cross-over  tube. The  ambient  air
sensor is located outside the control box so it can sense outdoor temperatures.

If the ambient sensor fails, the defrost control will initiate a defrost every 34 minutes of
compressor run time with the coil temperature below 35°F.

If the coil sensor fails, the defrost control will not initiate a defrost.

TEST MODE

The test mode is initiated by shorting the TEST pins. The unit must have an active heat
pump heating call to enter the test mode. In this mode of operation, the enable tem-
perature is ignored and all timers are sped up. To initiate a manual defrost, short and
hold the TEST pins. Remove the short when the system switches to defrost mode after
the compressor noise abatement delay. The defrost will terminate on time (14 minutes)
or when the termination temperature has been reached.

Test Sequence of Operation:

1) Provide a heating call to the heat pump.

2) Short test pins to bypass anti-short cycle timer. (If unit is running, this step is not

necessary.)

3) Short test pins and hold them shorted to enter defrost mode.

4) Release test pins once control exits noise abatement delay.

5) Monitor coil temperature when control exits defrost.

6) Unit should return to heating mode.

TROUBLE SHOOTING DEMAND DEFROST

During  the  test  mode  the  coil  temperature  should  be  monitored.  If  the  system  exits
defrost at approximately the termination temperature, the control is operating normlly.
If not, check the coil and ambient temperature sensor resistances, using the sensor
temperature vs. resistance table at the end of this section.

Immerse the sensor in water and measure the resistance of the sensor. At 35°F the
resistance of the sensor should be approximately 30,000 ohms.

Ensure that the coil sensor is properly installed that is not loose or touching the cabi-
net.

HIGH/LOW PRESSURE CONTROL MONITORING - ENHANCED
DEFROST CONTROL

Status  of  high  and  low  pressure  controls  is  monitored  by  the  enhanced  feature
demand defrost control and the following actions are taken.

High  Pressure  Control  – Provides  active  protection  in  both  cooling  and  heating
modes at all outdoor ambient temperatures. The high pressure control is an automat-
ic  reset  type  and  opens  at  approximately  610  psig  and  closes  at  approximately  420
psig. The compressor and fan motor will stop when the high pressure control opens
and will start again if the high side pressure drops to approximately 420 psig where the
automatic reset high pressure control resets. If the high pressure control opens 3 times
within a particular call for heating or cooling operation, the defrost control will lock out
compressor and outdoor fan operation.

Low  Pressure  Control  – Provides  active  protection  in  both  heating  and  cooling
modes at all outdoor ambient temperatures. The low pressure control is an automatic
reset type and opens at approximately 15 psig and closes at approximately 40 psig.
Operation is slightly different between cooling and heating modes.

Cooling Mode: The compressor and fan motor will stop when the low pressure
control opens and will start again when the low side pressure rises to approximate-
ly 40 psig after the low pressure control automatically resets. If the low pressure
switch opens 3 times within a particular call for cooling operation, the defrost con-
trol will lock out compressor and outdoor fan operation.

Heating  Mode: The  compressor  and  outdoor  fan  motor  will  stop  when  the  low
pressure  control  opens  and  will  start  again  when  the  low  side  pressure  rises  to

Summary of Contents for RJNL-B SERIES

Page 1: ...f r i h RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION DO NOT DESTROY THIS MANUAL PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCE BY A SERVICEMAN WARNING T...

Page 2: ...earances 13 Rooftop Installation 13 Ductwork 14 Filters 14 Cover Panel Installation Conversion Procedure 15 Condensate Drain 15 Condensate Drain Outdoor Coil 15 Electrical Wiring 15 Power Wiring 15 Co...

Page 3: ...he cabinet fan blade and coil with fresh water will remove most of the salt or other contaminants that build up on the unit 2 Regular cleaning and waxing of the cabinet with a good automobile polish w...

Page 4: ...ssure of R 410A is approximately 60 1 6 times greater than R 22 Recovery and recycle equipment pumps hoses and the like need to have design pressure ratings appropriate for R 410A Manifold sets need t...

Page 5: ...gned for R 410A 4 Tools Required For Installing Servicing R 410A Models Manifold Sets Up to 800 PSIG High side Up to 250 PSIG Low Side 550 PSIG Low Side Retard Manifold Hoses Service Pressure Rating o...

Page 6: ...RICAL ENTRY LOW VOLTAGE ELECTRICAL ENTRY POWER C O N D E N S E R C O I L SUPPLY AIR RETURN AIR FIGURE 1 UNIT DIMENSIONS BOTTOM VIEW FIGURE 2 UNIT DIMENSIONS BOTTOM VIEW ST A1125 02B ST A1125 09B Typic...

Page 7: ...125 03 ST A1125 08B OUTDOOR FAN 2 2 OUTDOOR FAN 1 1 3 OUTDOOR FAN 3 6 5 4 OUTDOOR FAN 5 OUTDOOR FAN 4 OUTDOOR FAN 6 OUTDOOR COIL SUPPLY AIR FILTER RACK RETURN COMPARTMENT COMPRESSOR 2 FIGURE 5 COMPONE...

Page 8: ...COMPRESSOR ACCESS OUTDOOR FANS FIGURE 7 UNIT DIMENSIONS COMPONENT ACCESS ST A1125 01B 1 2 3 4 5 6 OUTDOOR FAN 4 OUTDOOR FAN 1 OUTDOOR FAN 5 OUTDOOR FAN 6 OUTDOOR FAN 3 OUTDOOR FAN 2 CONTROL COMPARTMEN...

Page 9: ...trol TX Valves TX Valves TX Valves TX Valves Indoor Coil Fin Type Louvered Louvered Louvered Louvered Tube Type Rifled Rifled Rifled Rifled Tube Size in mm 0 375 9 5 0 375 9 5 0 375 9 5 0 375 9 5 Face...

Page 10: ...m 53 3 4 95 53 3 4 95 Rows FPI FPcm 1 22 9 1 22 9 Refrigerant Control TX Valves TX Valves Indoor Coil Fin Type Louvered Louvered Tube Type Rifled Rifled Tube Size in mm 0 375 9 5 0 375 9 5 Face Area...

Page 11: ...30 90 90 90 90 45 45 30 35 100 100 100 100 45 50 35 35 2 2 2 2 2 2 200 230 200 230 460 460 575 575 3 3 3 3 3 3 3450 3450 3450 3450 3450 3450 7 7 7 7 7 7 25 25 25 25 12 2 12 2 9 9 164 164 164 164 100...

Page 12: ...vibration slab should not be connected to building structure 3 The location of the unit should be such as to provide proper access for inspection and servicing 4 Locate unit where operating sounds wi...

Page 13: ...embly see Roofcurb Installation Instruc tions 4 If the roofcurb is not used provisions for disposing of con densate water runoff must be provided 5 The unit should be placed on a solid and level roofc...

Page 14: ...or crawl space should be insulated with at least 2 of insulation with vapor barrier One half to 1 thickness of insulation is usually sufficient for ductwork inside the air conditioned space Balancing...

Page 15: ...e of this unit some of the condensate line joints should assembled for easy removal and cleaning Use a thin layer of Teflon tape or paste on drain pan connections and install only hand tight Do not ov...

Page 16: ...screws previously removed d Connect the unit contactor wires 1L1 1L2 1L3 to the compressor fuse block on the heater kit e Re install the power entry panel run conduit and the proper size field wiring...

Page 17: ...STAT WIRING IN THIS CHASE TO CONTROL BOARD 2 CAP PLUGS BASE CONTROL ENTRY BASE POWER ENTRY FIGURE 17 THERMOSTAT CONNECTIONS DIAGRAMS R Y1 Y2 G C TERMINAL BLOCK ST A1125 36 00 ONLY USED ON DUAL FUEL OR...

Page 18: ...7 723 2748 744 2877 764 3003 785 3124 804 3265 823 3410 842 3559 860 3710 878 3865 895 4024 912 4185 929 4350 7200 3398 570 1897 595 2042 619 2185 643 2327 666 2466 689 2602 711 2737 732 2870 753 3000...

Page 19: ...ate_________________________________________ 8 Turn thermostat system switch to HEAT Unit compressors should stop Raise temper ature setting to above room temperature Unit should run in heating mode a...

Page 20: ...MAND DEFROST CONTROL AND HIGH LOW PRESSURE CONTROLS The demand defrost control monitors the outdoor ambient temperature outdoor coil temperature and the compressor run time to determine when a defrost...

Page 21: ...lly If not check the coil and ambient temperature sensor resistances using the sensor temperature vs resistance table at the end of this section Immerse the sensor in water and measure the resistance...

Page 22: ...he unit or by shorting the two defrost control pins together ENHANCED FEATURE DEFROST CONTROL DIAGNOSTIC CODES SENSOR TEMPERATURE VS RESISTANCE TABLE REPLACEMENT PARTS Contact your local distributor f...

Page 23: ...66 295 300 350 300 350 188 217 200 225 78 78 100 100 100 100 B180CM No Heat 81 81 100 100 100 100 81 81 100 100 100 100 CE20C 1 14 4 19 2 49 13 65 5 40 46 2 131 139 150 175 150 175 50 58 50 60 81 81 1...

Page 24: ...ier Incorrect voltage At compressor terminals voltage must be within 10 of rating plate volts when unit is operating Compressor short cycles Incorrect voltage At compressor terminals voltage must be 1...

Page 25: ...25...

Page 26: ...26 NOTE 15 TON UNIT DOES NOT HAVE OFM 2 5...

Page 27: ...URE PSIG INDOOR AMBIENT F DB SUCTION PRESSURE PSIG 115 105 95 85 75 65 55 200 220 240 260 280 300 320 340 360 380 400 420 440 460 480 500 520 540 560 100 120 140 160 180 200 220 60 65 70 75 80 240 260...

Page 28: ...28 CM 0913 RJNL SERIES 15 TON...

Reviews: