14
INSTALLATION
Interconnecting Tubing (cont.)
Example:
A 3-Ton heat pump unit is installed 50’
below the ID unit, requires a 75’ of 1/2” diameter
liquid line, and 4 90° LR elbows.
• Fitting Equivalent Length (ft.) = 4 x .9 = 3.6’
• Total Equivalent Length (ft.) = 75’ + 3.6’ = 78.6’
• Rounded-down value (ft.) = 75’
This application is acceptable because the 50’
vertical rise is less than the maximum rise of 75’ for
this application. The application is also considered
to have a long line set. Reference the long line set
section of the I&O for detail.
R-410A
System
Capacity
Model
Liquid Line
Size
Connection
Size (Inch
I.D.) [mm]
Liquid Line
Size (Inch
O.D.) [mm]
Liquid Line Size
Elevation (Above or Below) Indoor Coil
Total
Equivalent
Length - Feet [m]
25 [7.62]
50 [15.24]
75 [22.86]
100 [30.48]
125 [45.72]
150 [45.72]
175 [53.34]
200 [60.96]
225 [68.58]
250 [76.20]
275 [83.82] 300
[91.44]
Maximum
Vertical Separation - Feet [m]
37
3/8" [9.53]
1/4 [6.35]
25 [7.62]
N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R N/R
5/16 [7.94]
25 [7.62]
50 [15.24]
60 [18.29]
45 [13.72]
35 [10.67]
20 [6.1]
5 [1.52]
N/R N/R N/R N/R N/R
3/8 [9.53]
25 [7.62]
50 [15.24]
75 [22.86]
80 [24.38]
80 [24.38]
75 [22.86]
70 [21.34]
65 [19.81]
60 [18.29]
55 [16.76]
50 [15.24] 45
[13.72]
7/16 [11.12]
25 [7.62]
50 [15.24]
75 [22.86]
95 [28.96]
90 [27.43]
90 [27.43]
85 [25.91]
85 [25.91]
85 [25.91]
80 [24.38]
80 [24.38] 80
[24.38]
1/2 [12.71]
25 [7.62]
50 [15.24]
75 [22.86]
95 [28.96]
95 [28.96]
95 [28.96]
95 [28.96]
95 [28.96]
95 [28.96]
90 [27.43]
90 [27.43] 90
[27.43]
Long Line Set Applications
Long line set applications are de
fi
ned as applica-
tions that require accessories or alternate construc-
tion methods. The following are special consider-
ations that need to be addressed when installing a
long line set application:
• Additional refrigerant charge
• Fitting losses and maximum equivalent length
considerations
• Refrigerant migration during the o
ff
cycle
• Oil return to the compressor
• Capacity losses
• System oil level adjustment
Table 2 is used to determine if the application is
considered to have a long line set.
The region of
the chart that is shaded grey is considered to be
a long line set application.
Oil Level Adjustments for Long
Line Set Applications
Additional oil will need to be added for long line set
applications. (Ref. Table 2). Below is the equation for
the oil level adjustment and the compressor name
plate oil charge for the di
ff
erent od units.
Oil to be Added = [(Charge Adju OD
Unit Name Plate Charge (oz.)) x (0.022) – [(0.10) x
(Compressor Name Plate Oil Charge (oz.))]
Example:
An application requires 125ft of line set
with a liquid line diameter of 3/8”, Charge Adjust-
ment = 52.4 oz., Name Plate Charge = 107 oz.,
Name Plate Oil Charge = 25 oz., Oil to be Added =
((52.4 oz. +107 oz.) x .022) – (.10 x 25 oz.) = 1.0 oz.
OD Model
Compressor
Name Plate Oil
Charge (oz)
RP1336AC
ZP31K5E-TF5-13R 42
RP1342AC
ZP36K5E-TF5-13R 42
RP1348AC
ZP42K5E-TF5-13R
42
RP1360AC
ZP49K6E-TF5-130
42
RP1336AD
ZP31K5E-TFD-13R
42
RP1342AD
ZP36K5E-TFD-13R
42
RP1348AD
ZP42K5E-TFD-13R
42
RP1360AD
42
ZP49K6E-TFD-130
N
Y
N
Y
N
Y
Y
Y
Factory
Installed
CCH
(Exerpt from Table 2, page 17)
Tubing
OD Model
Compressor
Name Plate Oil
Charge (oz)
RP1436AC ZP31K5E-T5F-13R
42
N
RP1442AC ZP36K5E-TF5-13R
42
Y
RP1448AC ZP42K5E-TF5-13R
42
N
RP1460AC ZP49K6E-TF5-130
42
Y
RP1436AD ZP31K5E-TFD-13R
42
N
RP1442AD ZP36K5E-TFD-13R
42
Y
RP1448AD ZP42K5E-TFD-13R
42
Y
RP1460AD ZP49K6E-TFD-130
42
Y
RP1418AJ ZP16K5E-PFV-13R
21
N
RP1430AJ ZP25K5E-PFV-13R
25
N
RP1436AJ ZP31K5E-PFV-13R
21
N
RP1442AJ ZP21K6E-PFV-130
21
N
RP1442AJ ZP36K5E-PFV-13R
42
N
RP1448AJ ZP42K5E-PFV-13R
42
Y
RP1460AJ ZP49K6E-PFV-130
42
N
RP1436FC ZP31K6E-TF5-130
21
N
RP1442FC ZP36K5E-TF5-13R
42
N
RP1448FC ZP40K6E-TF5-130
42
Y
RP1460FC ZP49K6E-TF5-130
42
Y
RP1418FJ ZP14K6E-PFV-130
21
N
RP1424FJ ZP20K6E-PFV-130
21
N
RP1430FJ ZP24K6E-PFV-130
25
N
RP1436FJ ZP31K6E-PFV-130
21
N
RP1442FJ ZP36K5E-PFV-13R
42
N
RP1448FJ ZP40K6E-PFV-130
42
N
RP1460FJ ZP49K6E-PFV-130
42
Y
Factory
Installed
CCH