COOLING PERFORMANCE DATA—RQNA-B024
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
➀
wbE
71°F [21.7°C]
67°F [19.4°C]
63°F [17.2°C]
CFM [L/s]
900 [425]
800 [378]
700 [330]
900 [425]
800 [378]
700 [330]
900 [425]
800 [378]
700 [330]
DR
➀
.19
.16
.11
.19
.16
.11
.19
.16
.11
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
31.4 [9.20]
18.2 [5.33]
1.6
30.7 [9.00]
17.2 [5.04]
1.5
30.0 [8.79]
16.2 [4.75]
1.5
29.1 [8.53]
21.6 [6.33]
1.6
28.4 [8.32]
20.4 [5.98]
1.5
27.8 [8.15]
19.2 [5.63]
1.5
28.6 [8.38]
23.3 [6.83]
1.5
28.0 [8.21]
22.0 [6.45]
1.5
27.4 [8.03]
20.7 [6.07]
1.5
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
30.5 [8.94]
18.0 [5.28]
1.6
29.8 [8.73]
17.0 [4.98]
1.6
29.2 [8.56]
16.0 [4.69]
1.6
28.2 [8.26]
21.4 [6.27]
1.6
27.6 [8.09]
20.2 [5.92]
1.6
27.0 [7.91]
19.0 [5.57]
1.6
27.8 [8.15]
23.1 [6.77]
1.6
27.2 [7.97]
21.8 [6.39]
1.6
26.5 [7.77]
20.5 [6.01]
1.6
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
29.5 [8.65]
17.6 [5.16]
1.7
28.8 [8.44]
16.6 [4.86]
1.7
28.2 [8.26]
15.7 [4.60]
1.7
27.2 [7.97]
21.0 [6.15]
1.7
26.6 [7.80]
19.8 [5.80]
1.7
26.0 [7.62]
18.7 [5.48]
1.7
26.8 [7.85]
22.7 [6.65]
1.7
26.2 [7.68]
21.4 [6.27]
1.7
25.6 [7.50]
20.2 [5.92]
1.7
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
28.4 [8.32]
17.1 [5.01]
1.8
27.8 [8.15]
16.1 [4.72]
1.8
27.1 [7.94]
15.2 [4.45]
1.8
26.1 [7.65]
20.4 [5.98]
1.8
25.5 [7.47]
19.3 [5.66]
1.8
25.0 [7.33]
18.2 [5.33]
1.8
25.7 [7.53]
22.1 [6.48]
1.8
25.1 [7.36]
20.9 [6.13]
1.8
24.5 [7.18]
19.7 [5.77]
1.8
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
27.3 [8.00]
16.5 [4.84]
1.9
26.7 [7.83]
15.6 [4.57]
1.9
26.1 [7.65]
14.7 [4.31]
1.9
25.0 [7.33]
19.9 [5.83]
1.9
24.5 [7.18]
18.8 [5.51]
1.9
23.9 [7.00]
17.7 [5.19]
1.9
24.6 [7.21]
21.6 [6.33]
1.9
24.0 [7.03]
20.4 [5.98]
1.9
23.5 [6.89]
19.2 [5.63]
1.9
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
26.3 [7.71]
15.9 [4.66]
2.0
25.7 [7.53]
15.0 [4.40]
2.0
25.1 [7.36]
14.1 [4.13]
2.0
24.0 [7.03]
19.2 [5.63]
2.0
23.5 [6.89]
18.2 [5.33]
2.0
22.9 [6.71]
17.1 [5.01]
2.0
23.5 [6.89]
20.9 [6.13]
2.0
23.0 [6.74]
19.8 [5.80]
2.0
22.5 [6.59]
18.6 [5.45]
2.0
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
25.4 [7.44]
15.3 [4.48]
2.1
24.9 [7.30]
14.5 [4.25]
2.1
24.3 [7.12]
13.6 [3.99]
2.0
23.1 [6.77]
18.7 [5.48]
2.1
22.6 [6.62]
17.6 [5.16]
2.1
22.1 [6.48]
16.6 [4.86]
2.0
22.7 [6.65]
20.4 [5.98]
2.1
22.2 [6.51]
19.2 [5.63]
2.1
21.7 [6.36]
18.1 [5.30]
2.0
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
24.8 [7.27]
14.8 [4.34]
2.2
24.3 [7.12]
14.0 [4.10]
2.2
23.7 [6.95]
13.2 [3.87]
2.1
22.5 [6.59]
18.1 [5.30]
2.2
22.0 [6.45]
17.1 [5.01]
2.2
21.5 [6.30]
16.1 [4.72]
2.1
22.1 [6.48]
19.8 [5.80]
2.2
21.6 [6.33]
18.7 [5.48]
2.1
21.1 [6.18]
17.7 [5.19]
2.1
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
24.5 [7.18]
14.4 [4.22]
2.3
24.0 [7.03]
13.6 [3.99]
2.2
23.4 [6.86]
12.8 [3.75]
2.2
22.2 [6.51]
17.8 [5.22]
2.3
21.7 [6.36]
16.8 [4.92]
2.2
21.3 [6.24]
15.8 [4.63]
2.2
21.8 [6.39]
19.5 [5.71]
2.3
21.3 [6.24]
18.4 [5.39]
2.2
20.8 [6.10]
17.3 [5.07]
2.2
HEATING PERFORMANCE DATA—RQNA-B024
IDB
60°F [15.5°C]
70°F [21.1°C]
80°F [26.7°C]
CFM [L/s]
900 [425]
800 [378]
700 [330]
900 [425]
800 [378]
700 [330]
900 [425]
800 [378]
700 [330]
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
0
[-17.8]
Total BTUH [kW]
Power
7.8 [2.29]
1.2
7.7 [2.26]
1.2
7.6 [2.23]
1.3
7.1 [2.08]
1.4
7.0 [2.05]
1.4
7.0 [2.05]
1.5
5.8 [1.70]
1.5
5.8 [1.70]
1.6
5.7 [1.67]
1.6
5
[-15]
Total BTUH [kW]
Power
9.4 [2.75]
1.3
9.3 [2.73]
1.3
9.2 [2.70]
1.3
8.7 [2.55]
1.4
8.6 [2.52]
1.5
8.5 [2.49]
1.5
7.4 [2.17]
1.6
7.3 [2.14]
1.6
7.3 [2.14]
1.6
15
[-9.4]
Total BTUH [kW]
Power
12.4 [3.63]
1.3
12.3 [3.60]
1.3
12.2 [3.58]
1.4
11.7 [3.43]
1.5
11.6 [3.40]
1.5
11.5 [3.37]
1.5
10.4 [3.05]
1.6
10.3 [3.02]
1.7
10.2 [2.99]
1.7
10
[-12.2]
Total BTUH [kW]
Power
10.9 [3.19]
1.3
10.8 [3.17]
1.3
10.7 [3.14]
1.3
10.2 [2.99]
1.5
10.1 [2.96]
1.5
10.0 [2.93]
1.5
8.9 [2.61]
1.6
8.9 [2.61]
1.6
8.8 [2.58]
1.6
25
[-3.9]
Total BTUH [kW]
Power
15.4 [4.51]
1.4
15.3 [4.48]
1.4
15.1 [4.43]
1.4
14.7 [4.31]
1.6
14.6 [4.28]
1.6
14.4 [4.22]
1.6
13.4 [3.93]
1.7
13.3 [3.90]
1.7
13.2 [3.87]
1.7
35
[1.7]
Total BTUH [kW]
Power
18.6 [5.45]
1.4
18.4 [5.39]
1.4
18.3 [5.36]
1.5
17.9 [5.25]
1.6
17.7 [5.19]
1.6
17.6 [5.16]
1.7
16.6 [4.86]
1.7
16.5 [4.84]
1.8
16.3 [4.78]
1.8
20
[-6.7]
Total BTUH [kW]
Power
13.9 [4.07]
1.3
13.8 [4.04]
1.4
13.6 [3.99]
1.4
13.2 [3.87]
1.5
13.1 [3.84]
1.6
13.0 [3.81]
1.6
11.9 [3.49]
1.7
11.8 [3.46]
1.7
11.7 [3.43]
1.7
30
[-1.1]
Total BTUH [kW]
Power
17.0 [4.98]
1.4
16.8 [4.92]
1.4
16.7 [4.89]
1.4
16.3 [4.78]
1.6
16.1 [4.72]
1.6
16.0 [4.69]
1.6
15.0 [4.40]
1.7
14.9 [4.37]
1.7
14.7 [4.31]
1.8
40
[4.4]
Total BTUH [kW]
Power
20.3 [5.95]
1.4
20.2 [5.92]
1.5
20.0 [5.86]
1.5
19.7 [5.77]
1.6
19.5 [5.71]
1.7
19.3 [5.66]
1.7
18.4 [5.39]
1.8
18.2 [5.33]
1.8
18.1 [5.30]
1.8
50
[10]
Total BTUH [kW]
Power
24.3 [7.12]
1.5
24.1 [7.06]
1.5
23.9 [7.00]
1.5
23.6 [6.92]
1.7
23.4 [6.86]
1.7
23.2 [6.80]
1.7
22.3 [6.54]
1.8
22.1 [6.48]
1.8
21.9 [6.42]
1.9
45
[7.2]
Total BTUH [kW]
Power
22.2 [6.51]
1.5
22.0 [6.45]
1.5
21.8 [6.39]
1.5
21.5 [6.30]
1.7
21.3 [6.24]
1.7
21.2 [6.21]
1.7
20.3 [5.95]
1.8
20.1 [5.89]
1.8
19.9 [5.83]
1.8
IDB—Indoor air dry bulb
[
] Designates Metric Conversions
NOTES:
➀
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
10
SYSTEMS PERFORMANCE—RQNA-B SERIES
Summary of Contents for RQNA-B024JK
Page 22: ...22 TYPICAL INSTALLATIONS Designates Metric Conversions Designates Metric Conversions...
Page 31: ...31 WIRING SCHEMATICS RQNA B SERIES...
Page 32: ...32 WIRING SCHEMATICS RQNA B SERIES...
Page 33: ...33 WIRING SCHEMATICS RQNA B SERIES...
Page 34: ...34 WIRING SCHEMATICS RQNA B SERIES...
Page 35: ...35 NOTES...