12
SYSTEMS PERFORMANCE—RQNA-B SERIES
COOLING PERFORMANCE DATA—RQNA-B036
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
➀
wbE
71°F [21.7°C]
67°F [19.4°C]
63°F [17.2°C]
CFM [L/s]
1350 [637]
1200 [566]
1050 [496]
1350 [637]
1200 [566]
1050 [496]
1350 [637]
1200 [566]
1050 [496]
DR
➀
.19
.16
.11
.19
.16
.11
.19
.16
.11
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
46.3 [13.57]
26.6 [7.80]
2.4
45.3 [13.28]
25.1 [7.36]
2.4
44.3 [12.98]
23.7 [6.95]
2.4
43.0 [12.60]
31.7 [9.29]
2.4
42.1 [12.34]
29.9 [8.76]
2.4
41.1 [12.05]
28.2 [8.26]
2.3
41.4 [12.13]
33.4 [9.79]
2.4
40.4 [11.84]
31.5 [9.23]
2.4
39.5 [11.58]
29.7 [8.70]
2.4
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
45.2 [13.25]
25.8 [7.56]
2.6
44.2 [12.95]
24.4 [7.15]
2.5
43.2 [12.66]
22.9 [6.71]
2.5
41.9 [12.28]
30.9 [9.06]
2.5
41.0 [12.02]
29.2 [8.56]
2.5
40.1 [11.75]
27.5 [8.06]
2.5
40.3 [11.81]
32.6 [9.55]
2.5
39.4 [11.55]
30.8 [9.03]
2.5
38.5 [11.28]
29.0 [8.50]
2.5
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
43.9 [12.87]
25.1 [7.36]
2.7
42.9 [12.57]
23.8 [6.98]
2.6
41.9 [12.28]
22.4 [6.56]
2.6
40.6 [11.90]
30.2 [8.85]
2.6
39.7 [11.63]
28.5 [8.35]
2.6
38.8 [11.37]
26.9 [7.88]
2.6
38.9 [11.40]
31.9 [9.35]
2.7
38.0 [11.14]
30.2 [8.85]
2.6
37.2 [10.90]
28.4 [8.32]
2.6
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
42.4 [12.43]
24.6 [7.21]
2.8
41.4 [12.13]
23.3 [6.83]
2.8
40.5 [11.87]
21.9 [6.42]
2.7
39.1 [11.46]
29.7 [8.70]
2.8
38.2 [11.20]
28.0 [8.21]
2.7
37.3 [10.93]
26.4 [7.74]
2.7
37.4 [10.96]
31.4 [9.20]
2.8
36.6 [10.73]
29.7 [8.70]
2.7
35.7 [10.46]
27.9 [8.18]
2.7
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
40.8 [11.96]
24.1 [7.06]
2.9
39.9 [11.69]
22.8 [6.68]
2.9
39.0 [11.43]
21.5 [6.30]
2.9
37.5 [10.99]
29.2 [8.56]
2.9
36.7 [10.76]
27.6 [8.09]
2.8
35.8 [10.49]
26.0 [7.62]
2.8
35.8 [10.49]
30.9 [9.06]
2.9
35.0 [10.26]
29.2 [8.56]
2.9
34.2 [10.02]
27.5 [8.06]
2.8
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
39.3 [11.52]
23.6 [6.92]
3.0
38.4 [11.25]
22.3 [6.54]
3.0
37.5 [10.99]
21.0 [6.15]
3.0
36.0 [10.55]
28.7 [8.41]
3.0
35.2 [10.32]
27.1 [7.94]
3.0
34.4 [10.08]
25.5 [7.47]
2.9
34.3 [10.05]
30.4 [8.91]
3.0
33.5 [9.82]
28.7 [8.41]
3.0
32.8 [9.61]
27.0 [7.91]
2.9
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
37.8 [11.08]
23.0 [6.74]
3.2
37.0 [10.84]
21.7 [6.36]
3.1
36.2 [10.61]
20.5 [6.01]
3.1
34.5 [10.11]
28.1 [8.24]
3.1
33.8 [9.91]
26.5 [7.77]
3.1
33.0 [9.67]
25.0 [7.33]
3.0
32.9 [9.64]
29.8 [8.73]
3.1
32.1 [9.41]
28.1 [8.24]
3.1
31.4 [9.20]
26.5 [7.77]
3.1
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
36.6 [10.73]
22.2 [6.51]
3.3
35.8 [10.49]
21.0 [6.15]
3.2
35.0 [10.26]
19.8 [5.80]
3.2
33.3 [9.76]
27.3 [8.00]
3.2
32.6 [9.55]
25.8 [7.56]
3.2
31.8 [9.32]
24.3 [7.12]
3.2
31.6 [9.26]
29.0 [8.50]
3.3
30.9 [9.06]
27.4 [8.03]
3.2
30.2 [8.85]
25.8 [7.56]
3.2
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
35.7 [10.46]
21.3 [6.24]
3.4
34.9 [10.23]
20.1 [5.89]
3.4
34.1 [9.99]
18.9 [5.54]
3.3
32.4 [9.50]
26.3 [7.71]
3.4
31.7 [9.29]
24.9 [7.30]
3.3
30.9 [9.06]
23.4 [6.86]
3.3
30.7 [9.00]
28.0 [8.21]
3.4
30.0 [8.79]
26.5 [7.77]
3.3
29.3 [8.59]
25.0 [7.33]
3.3
HEATING PERFORMANCE DATA—RQNA-B036
5
[-15]
Total BTUH [kW]
Power
15.8 [4.63]
1.8
15.7 [4.60]
1.9
15.5 [4.54]
1.9
14.9 [4.37]
2.1
14.8 [4.34]
2.1
14.7 [4.31]
2.2
14.1 [4.13]
2.4
14.0 [4.10]
2.4
13.8 [4.04]
2.4
IDB
15
[-9.4]
60°F [15.5°C]
Total BTUH [kW]
Power
19.4 [5.69]
1.9
70°F [21.1°C]
19.2 [5.63]
2.0
19.1 [5.60]
2.0
80°F [26.7°C]
18.5 [5.42]
2.2
18.3 [5.36]
2.2
CFM [L/s]
18.2 [5.33]
2.3
17.7 [5.19]
2.5
1350 [637]
1200 [566]
1050 [496]
1350 [637]
1200 [566]
1050 [496]
1350 [637]
1200 [566]
1050 [496]
17.5 [5.13]
2.5
17.3 [5.07]
2.5
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
0
[-17.8]
Total BTUH [kW]
Power
13.9 [4.07]
1.8
13.8 [4.04]
1.8
13.6 [3.99]
1.8
13.0 [3.81]
2.0
12.9 [3.78]
2.1
12.7 [3.72]
2.1
12.1 [3.55]
2.3
12.0 [3.52]
2.4
11.9 [3.49]
2.4
10
[-12.2]
Total BTUH [kW]
Power
17.6 [5.16]
1.9
17.5 [5.13]
1.9
17.3 [5.07]
1.9
16.7 [4.89]
2.1
16.6 [4.86]
2.2
16.4 [4.81]
2.2
15.9 [4.66]
2.4
15.8 [4.63]
2.5
15.6 [4.57]
2.5
25
[-3.9]
Total BTUH [kW]
Power
23.0 [6.74]
2.0
22.8 [6.68]
2.1
22.6 [6.62]
2.1
22.1 [6.48]
2.3
21.9 [6.42]
2.3
21.7 [6.36]
2.4
21.3 [6.24]
2.6
21.1 [6.18]
2.6
20.9 [6.13]
2.6
35
[1.7]
Total BTUH [kW]
Power
27.3 [8.00]
2.1
27.1 [7.94]
2.2
26.8 [7.85]
2.2
26.4 [7.74]
2.4
26.2 [7.68]
2.4
25.9 [7.59]
2.5
25.6 [7.50]
2.7
25.3 [7.41]
2.7
25.1 [7.36]
2.7
20
[-6.7]
Total BTUH [kW]
Power
21.2 [6.21]
2.0
21.0 [6.15]
2.0
20.8 [6.10]
2.0
20.3 [5.95]
2.2
20.1 [5.89]
2.3
19.9 [5.83]
2.3
19.4 [5.69]
2.5
19.3 [5.66]
2.6
19.1 [5.60]
2.6
30
[-1.1]
Total BTUH [kW]
Power
25.1 [7.36]
2.1
24.8 [7.27]
2.1
24.6 [7.21]
2.1
24.1 [7.06]
2.3
23.9 [7.00]
2.4
23.7 [6.95]
2.4
23.3 [6.83]
2.6
23.1 [6.77]
2.6
22.9 [6.71]
2.7
40
[4.4]
Total BTUH [kW]
Power
29.9 [8.76]
2.2
29.6 [8.67]
2.2
29.4 [8.62]
2.2
29.0 [8.50]
2.4
28.7 [8.41]
2.5
28.5 [8.35]
2.5
28.1 [8.24]
2.7
27.9 [8.18]
2.7
27.6 [8.09]
2.8
50
[10]
Total BTUH [kW]
Power
36.3 [10.64]
2.3
35.9 [10.52]
2.3
35.6 [10.43]
2.3
35.4 [10.37]
2.5
35.0 [10.26]
2.6
34.7 [10.17]
2.6
34.5 [10.11]
2.8
34.2 [10.02]
2.8
33.9 [9.94]
2.9
45
[7.2]
Total BTUH [kW]
Power
32.8 [9.61]
2.2
32.6 [9.55]
2.3
32.3 [9.47]
2.3
31.9 [9.35]
2.5
31.7 [9.29]
2.5
31.4 [9.20]
2.6
31.1 [9.11]
2.8
30.8 [9.03]
2.8
30.6 [8.97]
2.8
IDB—Indoor air dry bulb
[
] Designates Metric Conversions
NOTES:
➀
When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power—KW input
Summary of Contents for RQNA-B024JK
Page 22: ...22 TYPICAL INSTALLATIONS Designates Metric Conversions Designates Metric Conversions...
Page 31: ...31 WIRING SCHEMATICS RQNA B SERIES...
Page 32: ...32 WIRING SCHEMATICS RQNA B SERIES...
Page 33: ...33 WIRING SCHEMATICS RQNA B SERIES...
Page 34: ...34 WIRING SCHEMATICS RQNA B SERIES...
Page 35: ...35 NOTES...