Installation, operating and maintenance manual SKIT/S-DEB
3rd print version
page 57
10 – Operation
RWO GmbH
●
Marine Water Technology
●
Bremen
●
Germany
Issue 2014-04-10
After pressing the Enter button:
Input mapping (see notes on input mapping
à
10.5.5
)
EING: 0. 0. 0. 0
0110.1011.0001.1000
IN: 0. 0. 0. 0
0110.1011.0001.1000
After pressing the Enter button:
Output mapping (see notes on output
mapping
à
10.5.6
)
AUSGANG:
1000.0111.00
OUT:
1000.0111.00
After pressing the Enter button:
Query branching to the user settings (see
à
10.5.7
)
KUNDENPARAMETER
AENDERN? NEIN JA
USER SETTINGS
MODIFY? NO YES
After pressing the Enter button:
Query branching to the factory parameters (RWO
service only)
WERKSPARAMETER
AENDERN? NEIN JA
FACTORY SETTINGS
MODIFY? NO YES
After pressing the Enter button:
Back to operation display
Language selection
10.5.4
In the display "language selection" select English with the
+button and German with the –button. Confirm the
selection with Enter and move on to the next main item in
the menu structure. Use ESC to interrupt the language
selection without changes.
Notes on input mapping
10.5.5
EING: 48. 0. 0. 65
0110.1011.0001.1001
IN: 48. 0. 0. 65
0110.1011.0001.1001
The first line contains 4 numbers separated by points. The
value range of each number is between 0 and 102. The
first two numbers belong to the two analogue inputs of the
sensor electrodes and mirror the percentage threshold of
the input parameter for maximum modulation. In case of a
0-10V input, the value 48 indicates approx. 4.8 V. The 3rd
and 4th digit reflect the resistances measured at the
sensor electrode inputs. 0 indicates no or low resistance
(water). High numbers (e.g. 65) indicate a high resistance
(oil).
The second line contains the On/Off state of the inputs,
indicated by 0 or 1. A total of 16 input data are displayed.