5
English |
Original instructions
ELECTRICAL
EXTENSION CORD CABLE SIZE
Refer to the table below to ensure the cable size of the extension cords you use are capable of carrying the required load.
Inadequate size cables can cause a voltage drop, which can damage the appliance and overheat the cord.
Current in
Amperes
Load in Watts
Maximum Allowable Cord Length
At 240 V
6.0 mm² Wire
4.0 mm² Wire
1.5 mm² Wire
1.0 mm² Wire
2.5
600
300 m
180 m
120 m
75 m
5
1200
150 m
90 m
60 m
40 m
7.5
1800
100 m
60 m
40 m
30 m
10
2400
75 m
45 m
30 m
15 m
15
3600
45 m
30 m
20 m
20
4800
40 m
20 m
25
6000
30 m
30
7200
20 m
40
9600
ELECTRICAL MOTOR LOADS
It is characteristic of common electric motors in normal operation to draw up to six times their full load running current while
starting. This table may be used to estimate the watts required to start electric motors; however, if an electric motor fails
to start or reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check the
requirements of the tool or appliance being used compared to the rated output of the generator.
Motor Size (HP)
Running Watts
Watts required to start motor
Universal
Capacitor
Split phase
1/8
275
N/A
850
1200
1/6
275
600
850
2050
1/4
400
800
1050
2400
1/3
450
950
1350
2700
1/2
600
1000
1800
3600
3/4
850
1200
2600
-
1
1100
N/A
3300
-
CAUTION
Operating voltage and frequency requirement of all electronic equipment should be checked prior to plugging them
into this generator. Damage may result if the equipment is not designed to operate within a ±10% voltage variation,
and ±3 Hz frequency variation from the generator name plate ratings. To avoid damage, always have an additional
load plugged into the generator if solid state equipment (such as a television set) is used. A power line conditioner is
recommended for some solid state applications.
there may be a risk of explosion of petrol fumes, leaking
gas or explosive dusts.
6. Electrocution can occur if generator is used in rain,
snow, or near water; keep this unit dry at all times.
7. The output of this generating set is potentially lethal.
The set shall not be connected to a fixed electrical
installation by fixed wiring except by an appropriately
licensed person. See instruction manual.
8. Product does not include ground rod or copper wire.
Consult an electrician for advice before grounding your
generator.
Summary of Contents for RGN3600B
Page 1: ...ORIGINAL INSTRUCTIONS Low Power Generating Set RGN3600B...
Page 4: ...Fig 4 Fig 5 Fig 6 11 8 9 6 10 Fig 7 Fig 8 16 15 13 12 17 14...
Page 5: ...Fig 9 7 13 12 14 Fig 10 2 Fig 11 20 19 18 21 Fig 12...
Page 6: ...Fig 13 Fig 15 Fig 16 Fig 17 Fig 14 22 28 26 27 29 24 25 23 30...
Page 21: ...WIRING DIAGRAM...
Page 22: ......
Page 23: ......