INSTALLATION—PNEUMATIC KILL SWITCH CHECK AND ADJUSTMENT
NOTE: If the reversing edge is set too sensitive,
the door may reverse direction during the
closing cycle, without the reversing edge
coming in contact with an object. If this
occurs, readjust the reversing edge
switch.
PNEUMATIC KILL SWITCH CHECK AND
ADJUSTMENT
A kill switch has been mounted in the bottom bar
assembly to prevent door operation if the breakaway
bottom bar becomes separated from either side column.
Kill Switch Check
Take precautions to prevent the door from
being opened or closed while performing
the following procedure.
1.
Raise or lower the door to approximately head or
chest height and stop the door.
NOTE: It should not be possible to restart the door
until the door has been reassembled and
the control system reset.
2.
Push the breakaway bottom bar out of the side col-
umn. Door should not operate until control box is
reset. (See Figure 35 and Figure 36.)
If the kill switch did not operate properly:
Adjust
the kill switch and then recheck it. (See “Kill Switch
Air Bleed Adjustment” on this page.)
If the kill switch operated properly:
Reinstall the
bottom bar into the side column. (See “RESET-
TING BOTTOM BAR ASSEMBLY” on page 16.)
Figure 35
Figure 36
Kill Switch Air Bleed Adjustment
1.
The kill switch is mounted in the bottom bar assembly,
on the same side as the door motor. To access the
switch, first remove the access cover. (See Figure 37.)
Figure 37
2.
Make sure the clear PVC hose is tight on the air
input post so that air leakage cannot occur and
vibration will not cause the hose to fall off. Also
make sure the hose is not kinked. (See Figure 38.)
Figure 38
3.
The air bleed has been set at the factory and should
not require adjustment. To adjust the air bleed, turn
the air bleed adjustment screws located on the front
and back of the switch fully clockwise, but do not
overtighten. Then turn each screw back counter-
clockwise one full turn. (See Figure 38.)
4.
To adjust the kill switch sensitivity, see “Kill Switch
Sensitivity Adjustment” on page 16.
A7500050
Bottom Bar
Plastic Tabs Out
of Side Column
Air Switch Bladder
A8500179
Bottom Bar Assembly
Breakaway Tabs
A7500198
Bottom Bar
Access Cover
A7500202
PVC Hose Must
Be Tight
on
Air Input Post
Kill Switch (On
Same Side as
Door Motor)
Air Bleed
Adjustment
Screw (One
on Front and
One on Back