For preventing electric shock and fire, the frame of PV module shall be  

grounded properly. [Please be sure to remove a coated portion when grounding,  

because the PV module aluminum frame is coated with anodizing.] 

Configuration 

Size and material 

remarks 

  M4 Bolt 

16mm 

  M4 Star washer 

  M4 Plat washer 

  M4 Cup washer 

  Grounding wire 

12AWG 

  M4 Plat washer 

G  

  M4 Nut 

Materials 

 *SUS304: Bolt, Nut, Washer (Steel Use Stainless) 
 *Grounding wire: Copper 
 

Torque: 0.9Nm ~ 1.1Nm 
 

For the detail of Earth, refer to NEC

(

National Electric Code

690  grounding PV 

arrays for special requirements. 

8. Grounding Method  

9. Detailed module specification 

 Electrical Specifications 

STC 

(Irradiance 1000W/m2 ,Module temperature 25℃, AP-1.5)

SN245P-10 SN250P-10 SN255P-10

Rated power(Pmax)

245 W

250 W

255 W

Voltage at Pmax(Vmp)

29.2 V

29.7 V

30.0 V

Current at Pmax(Imp)

8.39 A

8.42 A

8.50 A

Warranted minimum Pmax

245 W

250 W

255 W

Short-Circuit Current (Isc)

8.85 A

8.86 A

8.93 A

Open-Circuit Voltage (Voc)

37.3 V

37.3 V

37.6 V

Module Effeciency

15.00%

15.30%

15.61%

Operating module temperature

Maximum System Voltage

Maximum Series Fuse Rating

Maximum Reverse Current

Measurement tolerance

STC 

(Irradiance 1000W/m2 ,Module temperature 25℃, AP-1.5)

SN300P-10 SN305P-10 SN310P-10

Rated power(Pmax)

300 W

305 W

310 W

Voltage at Pmax(Vmp)

35.6 V

36.0 V

36.3 V

Current at Pmax(Imp)

8.44 A

8.47 A

8.54 A

Warranted minimum Pmax

300 W

305 W

310 W

Short-Circuit Current (Isc)

8.88 A

8.90 A

8.96 A

Open-Circuit Voltage (Voc)

44.9 V

45.1 V

45.4 V

Module Effeciency

15.38%

15.64%

15.89%

Operating module temperature

Maximum System Voltage

Maximum Series Fuse Rating

Maximum Reverse Current

Measurement tolerance

 

60cells

■ 72cells

-40℃ to +85℃

1000VDC (IEC)

15A

20.25A

±

2.5%

-40℃ to +85℃

 1000VDC (IEC)

15A

20.25A

±2.5%

Item 

Value

 

  Temperature coefficient of Isc 

0.052%/℃

 

  Temperature coefficient of Voc 

 -

0.312%/℃

 

  Temperature coefficient of power 

 -

0.429%/℃

 

  NOCT 

(Air 20 ; Sun 0.8kW/m2 ; Wind 1m/s) 

 45

±3℃

 

  Temperature Characteristics 

[Before installation] 

[After installation] 

Summary of Contents for SN245P-10

Page 1: ...INSTALLATION MANUAL INSTALLATION MANUAL PV Module Installation SN Model Version 1 0 2015 INSTALLATION MANUAL...

Page 2: ...and the actual installation use operation and maintenance should be performed by qualified personnel with electrical license 4 For the detailed quality warranty policy of the product please refer the...

Page 3: ...20 year s manufacturing technology and thorough quality management We S Energy Co Ltd will reward our customers by continuing to develop and produce good quality of product and consistently challenge...

Page 4: ...care is required for preventing corrosion contamination deterioration due to mishandling when you load outdoor load installation Store a module in an indoor warehouse before installing Always wear pr...

Page 5: ...ool on the module frame and surface Abrasion of the coated surface may lead to oxidize frames or reduce their strength The scratch of the surface may be the main cause of the module output degradation...

Page 6: ...tall on the vehicle car train etc or ship please request special modules 12 Snow water dust or other foreign substance on the surface may increase reflection of the light and eventually reduce the PV...

Page 7: ...d by S Energy and return it to S Energy for repair and replacement Material All the wire for the PV module connection should be configured with PV cable only Cable for PV double insulation UV resistan...

Page 8: ...on should be designed to satisfy the mechanical load of the site Operating temperature A ambient temperature of module installation site is limited by the minimum and maximum temperature as shown belo...

Page 9: ...the IEC61215 standard and S Energy Co Ltd recommends the following method of installing a frame hole As described in figure 1 an installation hole is inserted in the frame if the frame is randomly pro...

Page 10: ...245 W 250 W 255 W Short Circuit Current Isc 8 85 A 8 86 A 8 93 A Open Circuit Voltage Voc 37 3 V 37 3 V 37 6 V Module Effeciency 15 00 15 30 15 61 Operating module temperature Maximum System Voltage M...

Page 11: ...method is recommended by S Energy for the installation of the PV module on a roof in heavy snow regions Failure to remove accumulated snow on the PV module for long time may cause long term power redu...

Page 12: ...ion and method of clamp installation Module Clamp Assembly 3 Additional Grounding Methods Grounding lug Clamp installation location A position Confirm 7 mechanical installation module drawing Clamp wi...

Page 13: ...orn Germany Tel 49 6196 9540 111 3 Fax 49 6196 9985 778 E mail info europe s energy com SEAI America Inc dba S ENERGY America Address 18881 Von Karman Ave Suite 760 Irvine CA 92612 U S A Tel 1 949 281...

Reviews: