background image

3. Allow smoke from a cotton wick or a punk to enter the

detector’s  sensing  chamber  for  at  least  10  seconds.

 

When  sufficient  smoke  has  entered  the  chamber,  an

 

alarm  signal 

would  be  triggered  by  illuminating  t

he 

LED.  After 

the

  alarm

  is  triggered

,

  r

eset  each 

detector  and/or  control  unit  before

 

attempting  to 

test  the  additional  detectors  in  the  same

 

zone.  If  the 

alarm  fails  in  this  step,  it  indicates  a

 

defective unit, 

which 

would 

require service.

HEAT SENSOR TESTING 

T

o test the detector, it

 should be subject to a flow of 

warm  air  at  a  temperature  between 

284F  and  356F 

(

140

and  180.

C).

 Some domestic hair dryers can meet 

this

 requirement. Proceed as follows: 

1. Switch on the warm airflow and check that 

the 

temperature

 is correct and stable.

2.

3.

 

D

irect  the  airflow  at  the

 

guard  protecting  the 

thermistor.  The  detector  shoul

d be triggered 

within 30 

seconds.

 When 

the 

alarm  is  on,  immediately  remove  the 

heat

 

source  and  check  that  the  detector’s  red  LED 

is 

on

.

 

Reset the detector from the control panel.

4.

 If the detector fails 

to trigger the

 alarm within 30 

seconds

,

 it

 would mean that it should be returned to the 

distributor for servicing to adjust its sensitivity.

5.

 After  testing

,

 check  that  the  system  is  set  for 

normal

 

operation and notify the appropriate authorities 

that the

 

testing operation is complete and the system 

is active

 

again.

NOTES FOR USING DETECTOR 

The  National  Fire  Protection  Association  (NFPA) 

states  that  duct  smoke  detector  must  not  used  as  a 

substitute  for  open  area  smoke  detector

s

.  Duct 

smoke  detector

s  are

  solely  intended  to  use  in  the 

air  handing  equipments  for  such  purposes  like 

dampers  or shutting down the air handing units. 

NOT SUITABLE FOR INSTALLATION IN 

AREAS WHERE AIR VELOCITIES EXCEED 

300 ft/min.
MAINTENANCE

The  recommended  minimum  requirement  for  detector 

maintenance consists of an annual cleaning of

 the

 dust 

from the  detector  head  by  using  a  vacuum

ing routine 

compliant with the

  NFPA-72A standard. 

CAUTION:  DO  NOT  ATTEMPT  TO  REMOVE 

THE SCREWS  WHICH  HOLD  THE  ASSEMBLY 

OF 

THE 

SMOKE-SENSING CHAMBER AND PRINTED 

CIRCUIT  BOARD  (PCB).  THIS  ASSEMBLY  IS 

SEALED  FOR  YOUR  PROTECTION  AND  IS  NOT 

INTENDED TO  BE SEPARATED FOR SERVICING BY 

USERS.  OPENING  SUCH  ASSEMBLY  WILL  VOID 

THE WARRANTY. 

REFER TO  THE TECHNICAL  BUL

E

TIN  ISSUE 

NO. STSD20080702S01, REV.D, July 02, 2008 

SPECIFICATION

Model

2/4

wire 

Heat

Sensor

Setting

Voltage

DC

(Min./Max.) 

Standby 

Current

(Max.) 

Alarm

Current

(12/24V)

Surge

Current

(Max.)

Start-Up

Time

(Max.) 

Permissible

Current

(Max.) 

Cycle 

Time

Alarm

contact

Base

Model No. 

SF119-4H(12V) 

135

±

5

12V 

80

μ

30mA 

30 Sec.

1-3 Sec. 

Form A 

P/N854001 

SF119-4H(24V) 

135

±

5

24V 

80

μ

45mA 

30 Sec.

1-3 Sec. 

Form A 

P/N854001 

SF119-4 (12V) 

12V 

80

μ

30mA 

30 Sec.

1-3 Sec. 

Form A 

P/N854001 

SF119-4 (24V) 

24V 

80

μ

45mA 

30 Sec.

1-3 Sec. 

Form A 

P/N854001 

SF119-2HL 

135

±

5

10.8~33V  80

μ

22/55mA

160

μ

A

30 Sec.

80mA 

1-3 Sec. 

— 

P/N854001 

SF119-2L 

10.8~33V  80

μ

22/55mA

160

μ

A

30 Sec.

80mA 

1-3 Sec. 

— 

P/N854001 

SF119-2H 

135

±

5

10.8~33V  80

μ

22/55mA

160

μ

A

30 Sec.

80mA 

1-3 Sec. 

— 

P/N852001 

SF119-2 

10.8~33V  80

μ

22/55mA

160

μ

A

30 Sec.

80mA 

1-3 Sec. 

— 

P/N852001 

Remark: L-

 remote indicator output; 

H-

Heat sensor; 

AR-

Auto-reset;

B-

Sound

2-wire devices are UL Recognized, the 4-wire devices are UL Listed

Reviews: