Page 38 / 60
www.sise-plastics.com
3.2.2.2)
A
utomatic and manual setpoint
For each zone, the control system accepts 2 setpoints for the Standby state and 2 setpoints for the
Production state (§3.2.1), a temperature setpoint for automatic operation and a power setpoint for
manual operation.
Each zone can be operated either manually
or automatically
.
If the zone is con
fi
gured in automatic mode
and the system in Standby
, the setpoint applied
to the zone will be the temperature setpoint for the Standby state
.
If the zone is con
fi
gured in manual mode
and the system in Production
, the setpoint applied
to the zone will be the power setpoint for the Production state.
.
3.2.3)
A
larms
3.2.3.1)
V
iewing alarms
Current system alarms can be viewed in the "Alarms" view, "Table of active alarms" screen (§2.3.1.2).
On the "List of active alarms" page, you will see a list of all current alarms, even system alarms. Zones
without alarm, on the other hand, are not displayed. This page can be easier to read, especially for a
large number of zones.