15
G
PREMASGARD
®
711x
PREMASGARD
®
711x
(Range: 0...+ xx Pa)
After successful zero point calibration, the output voltage
is 0 V at 0 Pa pressure difference (with the offset knob
in central position)!
Output voltage 0...10 V
for pressure difference from 0 Pa to final value
PREMASGARD
®
711x
(Range: - xx ...+ xx Pa)
After successful zero point calibration, the output current
is 5 V at 0 Pa pressure difference (with the offset knob
in central position)!
Output voltage 0...10 V
for pressure difference - ΔP... +ΔP
PREMASGARD
®
711x
(Range: 0...+ xx Pa)
After successful zero point calibration, the output current
is 4 mA at 0 Pa pressure difference (with the offset knob
in central position)!
Output current 4...20 mA
for pressure difference from 0 Pa to final value
PREMASGARD
®
711x
(Range: - xx ...+ xx Pa)
After successful zero point calibration, the output current
is 12 mA at 0 Pa pressure difference (with the offset knob
in central position)!
Output current 4...20 mA
for pressure difference - ΔP... +ΔP
# 502
00 - 2020