Mounting and Installation

Putting in operation 

After switching on the device, a self-test and tempering period follows.  
This procedure takes 30  -  50 minutes,depending on the ambient conditions.  
During this time the output analogue voltage differs from the actual measured value.

Switching point setting 

A potential-free changeover contact is available as a switch output.  
A switching point between 10 % and 95 % of the measuring range can be selected using  
the SET potentiometer. The 10 % value is added to the fresh air limit of 400  ppm for CO

2

(600...1900  ppm with MR = 0...2000  ppm  or  900...4700  ppm with MR = 0...5000  ppm).
With other measurands, the corresponding lower limit is used directly as a basis.   
(VOC: 10...95 %, Temperature: +5...+48 °C, Humidity: 10...95% r.H.)
The assignment of the switch output to measurand is done via DIP switch (DIP 7 and DIP 8).

Offset 

Each measuring channel has a separate offset potentiometer for subsequent adjustment of the measurement.  
The adjusting range is ± 10 % of the measuring range.

Display 

In the first line, the 

measurements

 with the corresponding 

units 

  

( CO

2

 in 

ppm

, VOC in 

%

, temperature in 

°C

, relative humidity in 

%  r.H.

)  

are displayed in a cyclical series.

In the second line, the 

switching status of the relay

 is shown on the left as a circuit 

(full 

● 

= relay energised;  empty 

 = relay de-energised)  

followed by the corresponding 

indicator 

(

C

 for  CO

2

;  

V

 for VOC;  

T

 for temperature;  

H

 for relative humidity in 

%  r.H.

)  

and the 

switchpoint value

 is shown on the right.

Summary of Contents for AERASGARD RCO2-W

Page 1: ...RTM CO2 SD 0 10 V fixed Rxx CO2 W 0 10 V or 4 20 mA working resistance 800 selectable via DIP switches selected variant applies for all outputs with offset potentiometer 10 of the measuring range Rela...

Page 2: ...50 C 0 2000 5000 ppm 0 100 W 1501 61B8 7321 200 Outputs 0 10V or 4 20mA selectable via DIP switches selected variant applies for all outputs Standard room sensor RTM CO2 SD with fixed output 0 10 V E...

Page 3: ...FF OFF VOC 10 95 ON OFF Temperature 5 48 C OFF ON Humidity 10 95 r H ON ON Output DIP 9 Voltage 0 10 V default OFF Current 4 20 mA ON Note DIP 5 is not assigned 4 5 6 1 2 3 SET REL OFFSET ZERO CO CO V...

Page 4: ...ly of the DIP switch position Sufficient fresh air must be provided before and after the calibration procedure We recommend a fresh air supply of at least two hours before the calibration process The...

Page 5: ...surands the corresponding lower limit is used directly as a basis VOC 10 95 Temperature 5 48 C Humidity 10 95 r H The assignment of the switch output to measurand is done via DIP switch DIP 7 and DIP...

Page 6: ...everse polarity protection diode is integrated in this device variant This internal one way rectifier on AC supply voltage The output signal is to be tapped by a measuring instrument The output signal...

Page 7: ...es must only be connected to safety extra low voltage and under dead voltage condition To avoid damages and errors the device e g by voltage induction shielded cables are to be used laying parallel wi...

Reviews: